Norwegian Tax Authority - Oslo Norway
|
|
|
- Jared May
- 9 years ago
- Views:
Transcription
1 1. INTRODUCTION Norwegian Tax Authority - Oslo Norway PROJECT SUMMARY Year of construction No previous energy renovations SPECIAL FEATURES Main topics in the renovation are: High insulated pre fabricated façades Airtightness 0,6 h-1 Reduced surface to volumen ratio Energy recovery from data facility I basement of building High efficiency technical systems, COP cooling systems, efficient heat recovery, and low SFP ARCHITECT LPO Achitects AS, Oslo Project Management Optimoprosjekt Consultant Sweco, Multiconsult, Hambra, Energeticadesign Partners ENOVA, Norway, Future built, Norway OWNER Entra Eiendom as Brochure Arne Førland Larsen Contact: [email protected] IEA SHC Task 47 Renovation of Non-Residential Buildings towards Sustainable Standards
2 2. CONTEXT AND BACKGROUND BACKGROUND The building is situated in the center of Oslo, close to public transportation and to a highway with heavy traffic. The entire building has an area of m 2 (internal area without outer walls including basement m 2 ) The building is programmed for approximately 1300 person, which makes an average area of 27 m 2 pr. person. The organization have focus on low energy equipment, thin Client computers are used on all workplaces. Typical floor plan before refurbishment Typical floor plan after refurbishment OBJECTIVES OF THE RENOVATION Overall goals for the project are: Energy label A Passive house standard In addition to the overall goals: Entra environmental policy, a specific Environmental Quality Assurance Program and a Quality Control Plan, where stated for the project. Entra environmental policy states that all their projects should include environmental program and plans.
3 2. CONTEXT AND BACKGROUND 3 D model of building after refurbishment OBJECTIVES OF THE RENOVATION The objectives and focus areas are: Energy objectives, 50% demands of Norwegian building codes. Indoor climate, in average level 1/2 according to EN Low emission and sustainable materials Reduction on water use Building waste during entire life cycle Clean building processes Sustainable solution and materials with high durability Lowering energy for transportation in building construction stage, encourage public transportation and bicycling in maintaining stage Follow environmental quality control plan for following up and running assessments in all stages of the design process SUMMARY OF THE RENOVATION The overall expected percentage reduction in primary energy consumption is ~ 60%
4 3. DECISION MAKING PROCESSES The initial project objectives were to refurbish the interior of the building, and energy was not at the time the main objective. The energy goal was energy label B. Through a process with building owner and users, the ambition was increased to energy label A / Passive house. Public funding programs involved are granted for this project. ENOVA, a Norwegian funding program, will be funding 50% of the extra Investment to improve the energy design from building codes minimum to a 50% below. Maximum funding is limited to ~69 Euro/m 2 The project has been granted a maximum funding of Euro. Reduced operation using calculated payback time has been made for the application to Enova. Timeline for the decision making process Idea was born First brief project description completed Detailed project description completed Tendering process started Signing of contract with main contractor Start renovation Renovation completed Not completed Evaluation among occupants Not completed
5 4. BUILDING ENVELOPE Roof construction : U-value: < 0,12 W/m 2 K (average value) (Roof construction over basement 0,5-0,8 below terrain have now insulation before refurbishment. Average U value before refurbishment for roof 0,5 W/m 2 ) Wall construction : U-value: < 0,14 (average value above ground) U-value: < 0,47 (average value below ground) Windows: : U-value: < 0,72 (average value) Thermal bridge avoidance: Focus on thermal bridges in: Mounting of windows Insulation thickness where concrete slabs meets the façade Wood facade construction with few thermal bridges., and 200 mm insualtion in front of slabs. Overall demand to thermal bridges are: < 0,04 W/m 2 K Summary of U-values [W/m²K] Before Roof/attic ~ 0,2 1,0 (average 0,5) After 0,12 Floor/slab ~ 0,1 0,1 Walls ~ 0,2 0,4 0,17 Ceilings ~ 0,3 0,12 Windows ~1,8 0,72 Examples sections for walls
6 5. BUILDING SERVICES SYSTEM OVERALL DESIGN STRATEGY The overall design strategy based on: Optimizing the building envelope Optimizing technical system Utilization / recovery of energy from data facility in the building Reduced envelope to volume ratio and avoid cooling fingers LIGHTING SYSTEM The existing lighting system is a traditional system with an estimated LENI number ~25 kwh/m 2 year New lighting system has an estimated LENI number ~14 kwh/m 2 year HEATING SYSTEM Before - Electrical heating After - Water based heating systems COOLING SYSTEM Before Central cooling of inlet air for mechanical ventilation After Cooling system will be based on: Central AC mechanical ventilation Cooled beams in areas with high internal loads (in area with high cooling demands, meeting rooms and office areas with high internal loads)
7 5. BUILDING SERVICES SYSTEM HEATING SYSTEM Before - Electrical heating After - Water based heating systems VENTILATION Before CAV mechanical ventilation After VAV mechanical ventilation HOT WATER PRODUCTION Before - Central electrical heated boiler After - Central boiler heated with waste energy from data Facility in basement in combination with electricity/ district heating RENEWABLE ENERGY SYSTEMS Before none, all energy consumption was based on electrical supply. After - Reuse of waste energy from data facilities in basement in combination with district heating from public supply. Night cooling strategy for reduced cooling.
8 6. ENERGY PERFORMANCES Energy performance (kwh/m 2 ) Before: ~ 190 kwh/m 2 year ( measured ) ~ 174 kwh/m 2 year (estimated net energy consumption which is including sub consumptions according to Norwegian regulation, comparable with calculated consumption, see figure) ~170 kwh/m 2 year (estimated primary energy consumption which is including sub consumptions according to Norwegian regulation, comparable with calculated consumption, see figure) After: 88 kwh/m 2 year (calculated net) 84 kwh/m 2 year (calculated primary) Overall savings target : From: 190 / 170 kwh/m2 year To: 69 kwh/m2 year. Primary energy Savings target ~ 65% / 60% Energy budget - net energy/ space deliverable (calculated according to Norwegian Building codes) After Before Space heating 5,3 kwh/m² Mechanical ventilation - heating 5,9 kwh/m² Hot Water 5 kwh/m² Energy fans for mechanical ventilation 11,2 kwh/m² Energy pumps for heating, ventilation, cooling 1,8 kwh/m² Lighting 13,8 kwh/m² Technical equipmnet, PC, data etc. 34,5 kwh/m² Coooling, cooled beams in office areas 3,3 kwh/m² Cooling, central mechanical ventilation 6,9 kwh/m² Total netto energy demand 87,7 174 kwh/m² Energy deliverable (primary energy demand) Electricity kwh/m² District heating 4 0 kwh/m² Heat recovery from data facility in building 15 0 kwh/m² Total primary energy demand kwh/m² Conversion factors/ primary energy factors: Electricity 1 Heating 0,87 COP cooling 2,7 COP Heating 3
9 7 ENVIRONMENTAL PERFORMANCE Environmental quality plan in addition to energy Indoor Environment The Best possible indoor air quality should be assured by appropriate design that meets: Flexible technical system Low emission materials Focus on operation and maintenance Indoor thermal climate design criteria: 22 +/- 2 degree, minimum in winter Maximum 25 degrees C in summer, during business hours 8 am-4 pm On hot summer days, it is accepted that indoor temperature increases or decreases by 0.5 C per C outside increases above 25 C Indoor air quality CO 2 level not exceed 1000 ppm Lighting LUX level general lighting 300 LUX LUX level on desk / workplace 500 LUX Average daylight factor in working areas DF = 2. Water management water saving equipment, water saving toilets, nozzles and shower heads. Monitoring of water consumption Material Usage Low emission materials for a good indoor environment Use of health-and environmentally hazardous substances should be reduced to a minimum Wood materials will come from sustainable forestry Materials that represents high greenhouse gas emissions should be avoided, target for green house emission are 50% below normal building standard in Norway (Future Built objectives) Waste Management Health and environmentally hazardous substances in demolishing process has to be handled in an environmentally friendly way and in according to regulations. A minimum of 80% of the building and tearing waste should be sorted. Design should focus on efficient waste management in the operating stage. Transport Restriction of transport to and from the construction site It should be made attractive to use environmentally-friendly means of transport such as bicycles, electric cars and public transport. It should be added to facilitate video conferences Environmental monitoring in the execution phase of environment follow-up plan Environmental follow-up plan to detail targets / objectives, and to provide accountability and to milestones.
10 8. MORE INFORMATION RENOVATION COSTS All investments cost are based on extra investment from Norwegian standard regulation level (TEK 10), to passive house standard / energy label A. All extra cost will be subsidized with up to 60% Overview on measured used, estimated investments cost (budget), and payback time are shown in figure. Energy cost for calculating pay back time is: 0,125 Euro/ kwh Energy result: Annual consumption: Before: 170 kwh/m 2 Savings: TEK 10 level 27 kwh/m 2 TEK 10 standard building 143 kwh/m 2 Saving passive level 58 kwh/m 2 Recovery: 16 kwh/m 2 Passive house standard 69 kwh/m 2 Payback time 5 11 years Measure Describtion Amount Unit Extra Energy saving Energy saving Energy saving Payback investment saving time (budget) (budget) [Euro] [kwh/ year] [kwh/ m2 year] [euro/ year] [year] Building envelope: Walls above ground U- value improved from 0,22 in average m , to 0,14 W/m2 K Cold bridges Improved from 0,12 to 0,04 W/m2 K m , Roof U- value improve from 0,18 in average m , to 0,1 W/m2 K Roof basement Roof in basement belove ground level m , (facing ground), from 1,0 to 0,15 W/m2 K Air tight building Air tightness improve from 1,5 to m , ,6 h -1 (n 50 value) (volume building) Passive house windows U-value improved from 1,2 i average m , to 0,72 W/m2 K Floor facing outside U- value improved from 0,22 in average 450 m , above the ground to 0,13 W/m2 K Technical system and energy supply Heat recovery and Heat recovery on mechanical ventilation m 3 /h , VAV mechanical vent. improved from 70% to 85% in average. SFP Specific fanpower reduced from 2, m 3 /h , to 1,5 kw/ m3/s in average Efficient lighting Efficiency of lighting system improved m , from LENI 25 to 12,4 kwh/m2 year Energy supply System for heatrecovery from data m , facility in basement (water based heating system not included) All measurers together 74,0 Process planing quality ensurance Extra project planning cost, quality planning etc., course m workers on site. Overall budget investments cost Subsidized Pay back time with subsidizing ,6
School in Schwanenstadt, Austria
School in Schwanenstadt, Austria 1. INTRODUCTION PROJECT SUMMARY - building period 1960s - numerous expansions SPECIAL FEATURES - Renovation to meet Passive House Standard - decentralized ventilation system
Klosterenga, Oslo, Norway, 1998-2000 page - 1
Klosterenga, Oslo, Norway, 1998-2000 page - 1 Introduction Klosterenga is an urban revitalisation project close to the city centre of Oslo. The 3 apartments were built with a focus on energy saving. Next
IEA SHC Task 47 Renovation of Non-Residential Buildings towards Sustainable Standards
Date of revision: 15.6.2012 Osram Culture Centre Copenhagen, Denmark Valhalsgade 4, 2200 Copenhagen N 1. INTRODUCTION PROJECT SUMMARY Construction year: 1953 Energy renovation: 2009 No past energy renovations
The first apartment house renovation with Passive House components in Norway
14th International Passive House Conference Dresden, May 28, 2010 Michael Klinski Tor Helge Dokka The first apartment house renovation with Passive House components in Norway 168 flats, onebedrooms (55
Improving thermal insulation of concrete sandwich panel buildings
Improving thermal insulation of concrete sandwich panel buildings Jørgen Munch-Andersen Danish Building Research Institute, Aalborg University LCUBE conference, Vienna 17-18 April 2007 Outline A general
Energy Efficient HVAC-system and Building Design
Energy Efficient HVAC-system and Building Design Maija Virta 1, Harri Itkonen 1, Panu Mustakallio 1, Risto Kosonen 1 1 Halton Oy, Finland Corresponding email: [email protected] SUMMARY This paper
Case study on residential building renovation and its impact on the energy use and thermal comfort
Case study on residential building renovation and its impact on the energy use and thermal comfort Hanne Kauko, Maria Justo Alonso, Ole Stavset and Ingrid Camilla Claussen SINTEF Energy Research Motivation
Franciscan Monastery, Graz, Austria
Franciscan Monastery, Graz, Austria 1. INTRODUCTION PROJECT SUMMARY - first parts 1239 - main parts from 1250 to 1650 - protected monument SPECIAL FEATURES Mission of the Franciscans: conservation and
Directorate for the Built Environment Building Standards Division
Directorate for the Built Environment Building Standards Division Energy Management Solutions Ltd Investigation of measures to improve the energy performance of a existing building: Retail JUNE 2009 Report
Energy Efficiency in Buildings
Energy Efficiency in Buildings Supplemental Guide to SANS 10400-XA & SANS 204 V. 3.0 Registered to: The Drawing Studio Image: digitalart / FreeDigitalPhotos.net Report Date: 26 August 2014 Practice Name:
Extra Low Energy Housing in Ireland How far should we go to the Passive House? Jonathan Jennings Head of R&D Kingspan Century Homes
Extra Low Energy Housing in Ireland How far should we go to the Passive House? Jonathan Jennings Head of R&D Kingspan Century Homes Current Status % CO 2 emissions Transport 30% Agriculture 2% Housing
Dienstleistung. Certification as "Quality Approved Passive House" Criteria for Residential-Use Passive Houses
Passiv Haus Institut Passivhaus Dienstleistung GmbH Dr. Wolfgang Feist Rheinstr. 44/46 Rheinstr. 44/46 D-64283 Darmstadt D-64283 Darmstadt www.passiv.de www.passivhaus-info.de Certification as "Quality
1..GENERAL DATA 2. CLIMATIC DATA. Location
1..GENERAL DATA Location Szentendre, Downtown, Hungary Property Community centre of Szentendre, Public, Municipality of Szentendre Year of Building: End of 19th Century Present use (1) Community centre
Energy savings in the residential area are essential in
Overheating and insufficient heating problems in low energy houses up to now call for improvements in future Requirements for improved energy performance have shifted major focus on energy calculations
BYG DTU. Thermal properties of window frame Type 1 Sheet: 1. Type: Side, top and bottom profile. Source file: Format: dwg/dxf bmp
Thermal properties of window frame Type 1 Sheet: 1 Type: Side, top and bottom profile Profile: Frame profile made of wood and a GRP profile mounted with a sealed triple glazing unit. Materials: Wood GRP
FACTORS AFFECTING ENERGY CONSUMPTION OF BUILDINGS
FACTORS AFFECTING ENERGY CONSUMPTION OF BUILDINGS 1 Ralf Lindberg, Professor Minna Korpi, M.Sc. Juha Vinha, Dr.Tech. June 11, 2008 Department of Civil Engineering, Tampere University of Technology 2 BACKGROUND
Solar Homes Catch the Sun. Are you planning a new house? Discover how you can apply solar architecture principles to:
PASSIVE Solar Design Solar Homes Catch the Sun Are you planning a new house? Discover how you can apply solar architecture principles to: keep your heating bills to a minimum enjoy the comfort of a warm
Energy audit in Finland
Energy audit in Finland NorTech Oulu Lauri Mikkonen Energy Audit in Finland An energy audit tells about the energy efficiency and total energy consumption in a building, including all consumed heating,
Delivering on innovation and market uptake. Best-in-cases of nzeb. Ramon Pascual Bucharest May 8th, 2015
www.zebra2020.eu Delivering on innovation and market uptake. Best-in-cases of nzeb Ramon Pascual Bucharest May 8th, 2015 Outline nzeb Database Best in cases of nzeb Climates in Europe Preliminary results
Towards low energy buildings the development of building regulations in Norway. Clara Good, Norut Narvik Oulu, 27 May 2011
Towards low energy buildings the development of building regulations in Norway Clara Good, Norut Narvik Oulu, 27 May 2011 Presentation layout Norut Narvik Research Institute Background: buildings and energy
Green House, Hungary
Further information Skanska AB www.skanska.com Contact Noel Morrin, SVP Sustainability & Green Support [email protected] Green House, Hungary Case Study 109 Aspects of Sustainability This project
DK2 IEA. Replacing mechanical ventilation with natural ventilation at Enghøjskolen school in Denmark
IEA Energy Conservation in Buildings and Community Systems, Annex 36 Case studies overview Replacing mechanical ventilation with natural ventilation at Enghøjskolen school in Denmark 1 Photos DK2 Figure
Clean Energy Solutions Center IEA Technology Roadmap: Energy Efficient Building Envelopes Launch
Clean Energy Solutions Center IEA Technology Roadmap: Energy Efficient Building Envelopes Launch Didier Houssin and Marc LaFrance International Energy Agency 18 December 2013 Paris IEA/SPT Flagship Publication,
HOW AN ENERGY EFFICIENT HOME CAN HELP THE ENVIRONMENT
HOW AN ENERGY EFFICIENT HOME CAN HELP THE ENVIRONMENT During the last century, concern about the environment increased, as issues such as global warming and the Greenhouse Effect convinced us that the
RULES FOR THE SETTING UP OF SUSTAINABLE BRANCHES Summary
RULES FOR THE SETTING UP OF SUSTAINABLE BRANCHES Summary January 2013 TABLE OF CONTENTS INTRODUCTION... 3 GENERAL RECOMMENDATIONS... 3 Communication with customers in the field of environmental sustainability...
Improving comfort and energy efficiency in a nursery school design process S. Ferrari, G. Masera, D. Dell Oro
Improving comfort and energy efficiency in a nursery school design process S. Ferrari, G. Masera, D. Dell Oro Dept. Building Environment Science &Technologies Politecnico di Milano Italy Research funded
BEST 3, Atlanta, April 2012 Grahame E. Maisey, P.E.
A Methodology to Develop a Sustainable, High Performance Building Envelope BEST 3, Atlanta, April 2012 Grahame E. Maisey, P.E. We re Going To Reveal New Sustainable Truths and Expose Old Bogus Truths We
Passive & Active Design
Passive & Active Design CIBSE Building Simulations Group Peter A. Brown CEng, MBA October 2010 Introduction Passive & Active Design Introduction What are the interactions between passive and active design?
CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND?
Topic B3: Control of indoor environment CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND? Axel CABLE 1,*, Mads MYSEN 1,2, Kari THUNSHELLE 1 1 SINTEF,
Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer
Residential HVAC Load Sizing Training October 14, 2015 David Kaiser Green Code Plan Reviewer DCRA - Green Building Division Regulations of green codes including: Green Building Act Green Construction Code
Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now
Fact Sheet #6 Air Conditioning In this fact sheet you will discover: The opportunity for energy efficiency How air conditioning works Low cost actions to reduce energy usage now Investments to reduce costs
Data Collection Summary Report
Data Collection Summary Report Asilo Cologno Monzese Polo Territoriale per la Prima Infanzia con Asilo Nido 22/09/2011 The sole responsibility for the content of this report lies with the authors. It does
9 Energy management. 9:1 General. BFS 2011:26 BBR Oct. 9:11 Scope of application
BFS 2011:26 9 Energy management This section contains the provisions and general recommendations for Chapter 3, Article 14 and Chapter 3 the first paragraph of Article 15 of PBF. Section 9:9 contains provisions
Does Green Building pay? Danish decisions and German experiences Green Building Council Denmark and AHK in Copenhagen the 26.09.
Sustainable integrated planning of GreenBuildings Best practice of Sustainable Green Corporate Architecture with Energy Efficiency & Renewables Does Green Building pay? Danish decisions and German experiences
EnergyPro Building Energy Analysis. Assisted Living Building
EnergyPro Building Energy Analysis Assisted Living Building EnergyPro Building Energy Analysis for an assisted living building Project Scope The purpose of the EnergyPro energy model was to evaluate the
CO2 Emissions. Indirect CO 2. Emissions Electricity and Heat Production 25 % Direct Emissions AFOLU 24 % Energy 1,4% Buildings 6,4 % Industry 11 %
CO2 Emissions Direct Emissions AFOLU 24 % Buildings 6,4 % Transport 14 % 49 Gt CO2 eq (2010) Indirect CO 2 Emissions Electricity and Heat Production 25 % Energy 1,4% Industry 11 % Transport 0,3 % Industry
Ecofys VII U-Values for Better Energy Performance of Buildings
Ecofys VII U-Values for Better Energy Performance of Buildings Quantifying the potential I II III IV & V VI Climate Protection Regulation Cost Effectiveness Enlarged EU Price Scenario Key figures from
Assessment Methods. 15 th November 2010 Huw Jenkins Simon Lannon
Assessment Methods 15 th November 2010 Huw Jenkins Simon Lannon Assessment Methods Program Country Year Program Country Year 1 R-2000 Canada 1982 12 LEED US 2000 2 P-mark Sweden 1989 13 ECO-Quantum Netherlands
Challenging the possibilities
Passivhus Norden 2013 Challenging the possibilities Olav Langenkamp, Architect ETH-MAA, Langenkamp.dk Architects, Tigervej 26 8400 Ebeltoft Denmark, [email protected] Martin Wikkelsø Brandt, Cand. Polyt.
Low energy class 1 typehouses according to the Danish building regulations
Low energy class 1 typehouses according to the Danish building regulations Jørgen Rose, Senior Researcher, Department of Energy and Environment, Danish Building Research Institute, Aalborg University;
THE EFFECT OF WINDOW POSITION AND WINDOW SIZE ON THE ENERGY DEMAND FOR HEATING, COOLING AND ELECTRIC LIGHTING. R.M.J. Bokel
THE EFFECT OF WINDOW POSITION AND WINDOW SIZE ON THE ENERGY DEMAND FOR HEATING, COOLING AND ELECTRIC LIGHTING R.M.J. Bokel Department of Architecture, Delft Technical University, Delft, The Netherlands,
Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres
What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy
Design of a zero energy office building
Design of a zero energy office building at Haakonsvern, Bergen Client and Project leader: Forsvarsbygg PRL: Stema Rådgivning ARK: LINK Arkitektur RIV, RIE og RIB: Multiconsult Special consultant energy:
THE NATIONAL BUILDING REGULATIONS PART XA: ENERGY EFFICIENCY. Presentation by Peter Henshall-Howard: HEAD: BUILDING DEVELOPMENT MANAGEMENT.
THE NATIONAL BUILDING REGULATIONS PART XA: ENERGY EFFICIENCY. Presentation by Peter Henshall-Howard: HEAD: BUILDING DEVELOPMENT MANAGEMENT. A Diagrammatic representation of the relationship between the
Air Conditioning, Comfort and Energy in India s Commercial Building Sector
Air Conditioning, Comfort and Energy in India s Commercial Building Sector THINK.CHANGE.DO Leena Thomas Richard dedear Rajan Rawal Ashok Lall PC Thomas University of Technology, Sydney Sydney University
Before You Start an Energy Efficiency Retrofit The Building Envelope
ABOUT YOUR HOUSE Before You Start an Energy Efficiency Retrofit The Building Envelope The building envelope is the outer layer of the building that separates the indoor living space from the outdoor environment,
Mechanical and Natural Ventilation
BBSE3006: Air Conditioning and Refrigeration II http://www.hku.hk/bse/bbse3006/ Mechanical and Natural Ventilation Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong E-mail:
Innovative solution for heat recovery of ventilation air in older apartment buildings - with low intervention affecting the residents
Innovative solution for heat recovery of ventilation air in older apartment buildings - with low intervention affecting the residents Innovative solution for heat recovery of ventilation air in older apartment
2014 British Columbia Building Code Changes
District of Houston 250-845-2238 2014 British Columbia Building Code Changes A District of Houston interpretation of the 2014 Building Code Changes for 9.36 & 9.32 The following changes reflect the most
Dispelling the Solar Myth - Evacuated Tube versus Flat Plate Panels. W illiam Comerford Sales Manager Ireland Kingspan Renewables Ltd.
Dispelling the Solar Myth - Evacuated Tube versus Flat Plate Panels W illiam Comerford Sales Manager Ireland Kingspan Renewables Ltd. 1 The Kingspan Group Energy independent buildings for a sustainable
Module 3.7. Thermal bridging
Module 3.7 Thermal bridging Learning Outcomes On successful completion of this module learners will be able to - Describe construction details which influence thermal bridging. 2 Introduction to thermal
HEAT LOAD AND SOLAR GAIN PREDICTION FOR SOLID WALL DWELLINGS RETROFITTED WITH TRIPLE VACUUM GLAZING FOR SELECTED WINDOW TO WALL AREA RATIOS
HEAT LOAD AND SOLAR GAIN PREDICTION FOR SOLID WALL DWELLINGS RETROFITTED WITH TRIPLE VACUUM GLAZING FOR SELECTED WINDOW TO WALL AREA RATIOS Saim Memon Philip C. Eames Centre for Renewable Energy Systems
Passive House Projects in Norway an Overview
Passive Houses in Cold Climates SESSION 4 Passive House Projects in Norway an Overview Inger Andresen and Tor Helge Dokka, SINTEF Building and Infrastructure Architecture and Building Technology, N-7465
Condensing Boiler Efficiency
Condensing Boiler Efficiency Date: July 17, 2012 PRES E NT ED BY DO N L E O NA RDI LE O N A RD I I NC. HV AC T RAI N I N G & C ON SU LT IN G Concepts 1 The current state of evolution in boiler design 2
Greenhouse Gas Implications of HVAC Upgrades in Multi-Unit Residential Buildings
Greenhouse Gas Implications of HVAC Upgrades in Multi-Unit Residential Buildings J A NUARY 2015 INTRODUCTION This Research Report explores best practices and approaches for reducing greenhouse gas (GHG)
BPC Green Builders. Green building for new and existing homes. Health Comfort Energy
BPC Green Builders Green building for new and existing homes Health Comfort Energy Mechanical Systems Installed HVAC Systems Primary energy source large, roof mounted, solar thermal array (AET flat plate)
AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries
AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries Hot tips and cool ideas to save energy and money! Air conditioning units or systems are often used by foundries
Portuguese Certification System for Energy an Indoor Air Quality Statistical Information about the Portuguese Certification System
Portuguese Certification System for Energy an Indoor Air Quality Statistical Information about the Portuguese Certification System Manuel Casquiço/ ADENE Tabula Expert Workshop - Energy Assessment of National
BREEAM Refurbishment and Fit-out 2014 Briefings. Part of the BRE Trust
BREEAM Refurbishment and Fit-out 2014 Briefings Part of the BRE Trust BREEAM for Refurbishment and Fit-out Follows 2 years of development Draft scheme published and consultation from 19 th July 2014 Launched
IDA Early Stage Building Optimization (ESBO) User guide
IDA Early Stage Building Optimization (ESBO) User guide Version 1.09, Oct 2013 2 Contents What is IDA ESBO?... 4 How do I use IDA ESBO?... 4 IDA ESBO user interface... 7 Rooms tab... 7 Building tab...
A comparative study of energy certification systems for buildings
A comparative study of energy certification systems for buildings Jelena Milicevic Master's Thesis Submission date: April 2014 Supervisor: Vojislav Novakovic, EPT Norwegian University of Science and Technology
De energievoorziening in 2040;
De energievoorziening in 2040; decentraal, duurzaam en intelligent! Prof. Dr. Ad van Wijk 25-6-2012 20-06-2012 Delft University of Technology Challenge the future There is no energy crisis Energy efficiency
The Reunion experience
Barcelona Workshop Experience on Net Zero Energy Buildings October 3rd 2012 1 The challenge of designing Net Zero Energy Buildings in Tropical Climates The Reunion experience Prof. François GARDE, PhD,
Achieving Net Zero. Bradley Berneche, President Alouette Homes. National Marketing Committee Canadian Home Builders Association Ottawa, June 6, 2008
Achieving Net Zero Bradley Berneche, President Alouette Homes National Marketing Committee Canadian Home Builders Association Ottawa, June 6, 2008 Overview Who Is Alouette Homes? The EQuilibrium Initiative
PROBIS SUPPORTING PUBLIC PROCUREMENT OF BUILDING INNOVATIVE SOLUTIONS
PROBIS SUPPORTING PUBLIC PROCUREMENT OF BUILDING INNOVATIVE SOLUTIONS Regione Lombardia ALER Bergamo Lecco Sondrio Treviglio via Dei Mulini n. 10/20 via Filzi n. 11/13 Prospectus Template provided by TEH-Ambrosetti.
D5.3 Energy audit report
Project Acronym: EPLACE Project Title: Eco public PLAtform for smart green CityzEn s living labs Call identifier: CIP-ICT-PSP Call 6 Theme 1: ICT for SMART CITIES Objective1.1: Smart Urban digital services
Sustainable Strategies for Rehabilitation Projects: 9th Street Office Building Adaptive Reuse Case Study
Sustainable Strategies for Rehabilitation Projects: 9th Street Office Building Adaptive Reuse Case Study Robert C. Burns, AIA, LEED AP Principal Director of Historic Architecture 804. 648. 5040, ext. 1107
Passive house rehabilitation of post war residential building in Zug, Switzerland
Passive house rehabilitation of post war residential building in, Switzerland Owner: Erbengemeinschaft Ducret Architect: Miloni & Partner, Wettingen Energy concept designer: Zurfluh & Lottenbach, Luzern
Passiv Haus Institut. Certification as "Quality Approved Passive House" Criteria for Residential-Use Passive Houses
Passiv Haus Institut Dr. Wolfgang Feist Rheinstr. 44/46 D-64283 Darmstadt www.passiv.de Certification as "Quality Approved Passive House" Criteria for Residential-Use Passive Houses Passive Houses are
WORKSHOP: The roles of wood in green building and green building effects on the forest sector of in the UNECE region.
WORKSHOP: The roles of wood in green building and green building effects on the forest sector of in the UNECE region. Are ENGO s ready to promote the use of wood as the preferred building material? Alison
Integrated Solar Radiant Systems
Integrated Solar Radiant Systems William Shady PE President Topics Radiant heating Indoor air quality Radiant Cooling Project Photos Questions and answers The goal for our clients Healthy Comfort Why Radiant
Rainwater Harvesting
Rainwater Harvesting With climate change now a reality rather than a speculated possibility, the demand on water resources has gone up, whilst the amount of water available for supply has gone down. Forth
Distributed Energy Systems
VTT TECHNICAL RESEARCH CENTRE OF FINLAND LTD Distributed Energy Systems Kari Sipilä, Principal Scientist VTT, Smart Energy Systems What is DESY DESY is R&D program for local energy systems covering the
Introduction to DEAP for Professionals DWELLING ENERGY ASSESSMENT PROCEDURE (DEAP)
Introduction to DEAP for Professionals Introduction to DEAP for Professionals 1 DWELLING ENERGY ASSESSMENT PROCEDURE (DEAP) 2 Introduction to DEAP for Professionals Introduction to DEAP for Professionals
Industrial Green Building Retrofit 101 Opportunities and Challenges. Light Industrial Green Building Retrofits. Why Green Retrofit?
Industrial Green Building 101 Opportunities and Challenges Joanne Sawatzky Senior Project Manager, Light House Sustainability at Work Re-visioning a Sustainable False Creek Flats Light Industrial Green
BCA Green Mark for Restaurants
BCA Green Mark for Restaurants Updated: 10/5/2011 1 Point Allocations - BCA Green Mark for Restaurants (I) Energy Related Requirements Part 1 : Energy Efficiency Category Point Allocations Minimum 20 points
HVAC Costs. Reducing Building. Building owners are caught between two powerful forces the need to lower energy costs. By Stephen J.
Reducing Building HVAC Costs of site rec By Stephen J. Pargeter Building owners are caught between two powerful forces the need to lower energy costs and the need to meet or exceed outdoor air ventilation
Holistic Approach in Delivering Government Buildings The Low Carbon Concept
International Conference on Planning for Low Carbon Cities 22 May 2009 Holistic Approach in Delivering Government Buildings The Low Carbon Concept Ir. HO Sai-king, Assistant Director (Building Services),
Green Affordable Housing Development Case Eco-Viikki, Finland
Green Affordable Housing Development Case Eco-Viikki, Finland Heikki Rinne Project Manager June 25, 2009, Washington D.C. 7.10.2008 Taske /KM/MHL Information on Helsinki Population Total 576,600 Men 47
Energy-Plus Primary School, Hohen Neuendorf, Germany
Energy-Plus Primary School, Hohen Neuendorf, Germany Ingo LÜTKEMEYER, Prof. Dipl.-Ing. Architekt BDA 1 Jens KRAUSE, Dipl. Ing. 2 Günter LÖHNERT, Dr. Ing. 3 Holger KÖNIG, Dipl.-Ing. 4 Detlef HENNINGS, Dr.
Building Energy Labels: The Swiss MINERGIE Label
Building Energy Labels: The Swiss MINERGIE Label Chennai, October 8 th, 2010 Heinrich Gugerli, Head Sustainable Building Group [email protected] www.stadt-zuerich.ch/nachhaltiges-bauen Energy
State of Connecticut Department of Public Health RADON PROGRAM
State of Connecticut Department of Public Health RADON PROGRAM Scope The Connecticut Department of Public Health (DPH) Radon Program is providing this information for contractors who decide to build radon
Archant London Environmental Awards
Archant London Environmental Awards Environmental Business of the Year Big Yellow Self Storage PLC Barking Central, Hertford Road, Barking, IG11 8BL Introduction Big Yellow is a local business that has
Sea Water Heat Pump Project
Sea Water Heat Pump Project Alaska SeaLife Center, Seward, AK Presenter: Andy Baker, PE, YourCleanEnergy LLC Also Present is ASLC Operations Manager: Darryl Schaefermeyer ACEP Rural Energy Conference Forum
Exemplary Retrofitting of an Old School in Stuttgart - EROS -
Exemplary Retrofitting of an Old School in Stuttgart - EROS - City of Stuttgart, Summary The objective of the project was to demonstrate the potentials of a retrofitting process for a typical school in
Home Energy Efficiency and Conservation: Call to Action. July 23, 2015 Dave Blake and David Wood REEP Green Solutions
Home Energy Efficiency and Conservation: Call to Action July 23, 2015 Dave Blake and David Wood REEP Green Solutions Today s Agenda Background Understanding where you are: Energy Usage EnerGuide Home Energy
Energy Management in Wuppertal
Energy Management in Wuppertal Organisation, Implementation and Financing Christian Gleim Gebäudemanagement der Stadt Wuppertal (GMW) 1 What do I want to tell you? Initial situation in Wuppertal Organisation
Heat pumps: better by nature
Heat pumps: better by nature For office buildings, hospitals, swimming pools, Heat, more than 80% of our energy consumption The burning of fossil fuels to meet our energy demand is resulting in the emission
HEAT PUMP FOR DISTRICT COOLING AND HEATING AT OSLO AIRPORT, GARDERMOEN
HEAT PUMP FOR DISTRICT COOLING AND HEATING AT OSLO AIRPORT, GARDERMOEN Geir Eggen 1 and Geir Vangsnes² 1) COWI AS. PB 254 Sentrum, N-7414 Trondheim. 2) Oslo Lufthavn AS, Edvard Munchsvei, 2 Gardermoen.
