Dubai Municipality Standard DMS 1: Part 5: 2004
|
|
|
- Briana Millicent Wright
- 9 years ago
- Views:
Transcription
1 Specification for precast concrete blocks Part 5: Normal-weight concrete-polystyrene sandwich masonry blocks Issue Date Revision Revision Description Prepared by Approved by Authorized by 19/12/2004 Issue for use This document is the property of Dubai Municipality and its issue is controlled. No part of this document should be reproduced or copied without the prior written permission of Dubai Central Laboratory Department.
2 Table of Contents Page Foreword ii 1 Scope 1 2 References 1 3 Definitions 1 4 Materials 1 5 Polystyrene core properties 2 6 Sandwich block properties 3 7 Sampling for tests 4 8 Intended use 4 Annex A: Site application of Sandwich-block 6 Table 1 Dimensions of Sandwich-blocks 3 Figures 1 Example of polystyrene core 2 2 Example of a Sandwich-block 3 i Issue Date 19/12/2004
3 Foreword With a view to having a comprehensive set of unified Dubai Municipality Standards which would be consistent and appropriate to local conditions and yet be at par with International Standards, the Dubai Central Laboratory Department is formulating standards taking guidance as much as possible from International and Regional Norms. This Standard sets the minimum requirements for a new type of precast concrete masonry block that is introduced in the local market to be used as thermal insulating block. Besides the basic requirements of the block, this Standard addresses the connectivity and stability requirements of a wall constructed using this type of block. This Standard also includes an annex for the site applications of the thermal insulatingblocks. Request Number: S RS Standards Committee: Dr. S. M. K. Chetty RSMO / DCL (Head of Committee) Aslam Riaz EMS / DCL (Member) Sameer Darwish EMS / DCL (Member) Khalil Al Mubayed I&CU / DCL (Member) Khader Akkawi RSMO / DCL (Coordinator) Amendments issued since publication Amd No. Date Text affected ii Issue Date 19/12/2004
4 1 Scope This standard specifies materials and minimum performance levels for precast concretepolystyrene masonry Sandwich-blocks. Also addresses the connectivity and stability requirements of a wall constructed using this type of block 2 References This standard incorporates provisions from other references. These references are cited undated at the appropriate points in the text, but latest edition of these references applies (including amendments). The titles of these references are listed on the last page. 3 Definitions 3.1 Normal weight concrete Concrete having an oven-dry density greater than 2000 kg/m 3 but not exceeding 2600 kg/m Expanded polystyrene Rigid cellular plastic material, manufactured by molding beads of expandable polystyrene or one of its copolymers, with an air filled closed cellular structure. 3.3 Extruded polystyrene Rigid cellular plastics insulation material expanded and extruded with or without a skin, from polystyrene or one of its copolymers and which has a closed cell structure 3.4 Sandwich-block A precast concrete block consisting of two outer leaves of normal weight concrete sandwiching a polystyrene core. 3.5 Lot The term Lot refers to any number of Sandwich- blocks of a specific configuration or dimension manufactured by the producer using the same materials, concrete mix, manufacturing process, and curing method. 4 Materials 4.1 Binders Precast concrete portion of Sandwich-blocks shall be made using Portland cement of type CEM 1 to BS EN 197 Part Aggregates The normal-weight aggregates used shall conform to the requirements of BS EN and the recommendations of PD 6682 Part 1, except for the grading requirement. 4.3 Admixtures The admixtures used shall be free from chlorides and conform to BS EN 934: Part Water The water used shall be clean and free from any deleterious and organic matter, and conform to BS EN Issue Date 19/12/2004
5 4.5 Thermal insulation core Thermal insulation core of the sandwich block shall be made of either expanded polystyrene or extruded polystyrene that complies with the requirements of clause (5) of this Specification and shall be certified by Dubai Municipality.. 5 Polystyrene core properties 5.1 Size and shape Polystyrene core of the Sandwich-block shall have the same length and height of the overall concrete dimensions. Polystyrene core thickness, when measured at any point, shall not be less than 60 mm. Polystyrene core shall have a dovetailing shape as shown in Fig. 1. Other shapes can also be used. Polystyrene core shall be either molded or extruded to shape without cutting. Fig. 1: Example of a polystyrene core 5.2 Apparent density When tested in accordance with BS EN 1602, for a sample of five specimens, the average apparent density shall be not less than 25 kg/m Thermal conductivity Thermal conductivity of the polystyrene core shall be declared by the polystyrene manufacturer according to BS EN ISO at 35ºC and 60% relative humidity (RH). When tested in accordance with BS EN or ASTM C 518, at 35ºC & 60% RH, polystyrene core thermal conductivity shall not exceed the declared value. 5.4 Reaction to fire Polystyrene shall be of the flame-retardant type. When tested in accordance with BS EN , the flame spread shall not exceed 150 mm within 60 s. Alternatively, the Oxygen index shall no be less than 24% by volume when tested in accordance with ASTM D Issue Date 19/12/2004
6 6 Sandwich block properties 6.1 Sizes Dimensions Sandwich-block overall dimensions shall conform to the requirements of Table 1. If air cavities exist in any of the two concrete leaves of the Sandwich-block, the shell thickness shall not be less than 20mm. A sample block is shown in Fig. 2. Table 1 - Dimensions of Sandwich-blocks Sandwich-block sizes Length (mm) Height (mm) Thickness (mm) Note: Other dimensions can be declared by the manufacturers. Fig. 2: Example of a Sandwich-block Tolerances When measured in the manner described in BS 6073: Part 1 appendix A, the length, height or thickness of each block from the sample shall not differ by more than ± 3 mm from the stated dimensions. 6.2 Manufacturing Sandwich-blocks are manufactured using normal weight concrete cast integrally with the dovetailed polystyrene core placed in the mould and wet concrete poured around it. The 3 Issue Date 19/12/2004
7 concrete is then compacted and cured. These processes are to be carried out without damage to the polystyrene core. 6.3 Chloride and sulfate content When tested in accordance with BS 1881 : Part 124, the acid soluble chloride (Cl) and sulfate (SO 3 ) content of Sandwich-blocks concrete shall not exceed 0.06% and 0.4% by dry mass of concrete respectively. 6.4 Compressive strength When tested in accordance with appendix B of BS 6073: Part 2, for a sample of ten Sandwich-blocks, the average compressive strength and that of an individual specimen, based on the gross area, shall be not less than the following: Average compressive strength: 7.5 N/mm 2 Individual compressive strength: 6.0 N/mm 2 Sandwich-blocks shall maintain their integrity during the compressive strength test i.e. failure pattern during compressive strength test shall not show evidence of separation between the polystyrene core and the outer concrete leaves. Any evidence of separation noticed before or during the test shall be a cause for rejection of the lot represented by the sample. 6.5 Thermal properties Thermal conductivity of the Sandwich-blocks shall be declared by the block manufacturer according to BS EN ISO at 35ºC and 60% relative humidity (RH). When tested in accordance with BS EN or BS EN or BS EN 1934 or BS EN ISO 8990 or ASTM C 1363, at 35ºC and 60% RH, Sandwich-block thermal conductivity shall not exceed the declared value. As an alternative, thermal conductivity of the Sandwich-blocks shall be calculated according to BS EN ISO 6946 taking into consideration the block configuration, concrete and polystyrene thermal conductivities declared by their manufacturers at 35ºC & 60% RH. 7 Sampling for tests 7.1 Number of Specimens The number of specimens required for each specified test shall be : - Sandwich-block dimensions and Compressive strength 10 blocks - Sandwich-block Concrete Chloride and Sulfate content 1 block - Sandwich-block thermal conductivity or Concrete thermal conductivity As required by the testing laboratory - Polystyrene core dimensions and apparent density 5 core specimens - Polystyrene core thermal conductivity 1 core specimen 4 Issue Date 19/12/2004
8 7.2 Selection of test specimens A representative sample of Sandwich-blocks required for test purposes shall be selected at random from every designated lot of 20,000 Sandwich-blocks or fraction thereof. Each specimen shall be marked so that it may be identified at any time. 8 Intended use Sandwich-blocks are intended to be used as thermal insulating blocks for the construction of infill, non-load bearing, masonry walls in buildings. Sandwich-blocks shall be used in superstructures only and shall not be used in substructures. 5 Issue Date 19/12/2004
9 Annex A: Site application of Sandwich-blocks A- Site storage Ultra-Violet light adversely affects the polystyrene properties. Therefore, polystyrene cores should be stored or kept in closed places unexposed to solar radiation. Also, Sandwichblocks need to be protected from exposure to solar radiation during their storage and handling until the time of erection where the polystyrene is then fully protected. B- Handling Sandwich-blocks need to be handled with care to avoid damage such as chipping of edges and corners, splitting between the polystyrene core and the outer concrete layers, etc. C- Thermal bridging Mortar joints in masonry walls built with Sandwich-blocks will act as a thermal bridge due to the high thermal conductivity of the mortar compared to the polystyrene core. To avoid this thermal bridge, 45 mm wide Polystyrene strips, having a thickness equal to the mortar joints thickness, may be included in the horizontal and vertical mortar joints to provide continuity for the Polystyrene thermal insulation layer. As an alternative, light weight aggregate concrete mortar with low thermal conductivity can be used as full bed mortar joints without any polystyrene strips. Other alternatives can also be used. D- Installation Care should be taken to align the blocks both horizontally and vertically in a way that the polystyrene cores of adjacent blocks are not staggered. This is of great importance so as to avoid forming thermal bridges inside the walls. E- Reinforcement E/1- Polystyrene may loose its adhesion with the concrete with time leaving the two concrete leaves of the Sandwich-block apart without any connection. To ensure the connectivity of the two concrete parts together, the methods discussed in clause (E/2) can be applied. E/2- Methods of connection: - Alkali resistant fiber mesh reinforcement 150 mm wide, or galvanized metal mesh or ladder type wire mesh reinforcement 150 mm wide, embedded in the mortar joints at every third course mm long ties complying with the requirements of BS EN 845: Part 1 shall be placed in mortar joints at a rate not less than 4.9 ties per one square meter of wall area. - Other methods for ensuring connectivity may be used. 6 Issue Date 19/12/2004
10 E/3- Column-masonry junctions shall be connected by galvanized wall ties, 2.5 mm x20 mm x 150 mm, complying with the requirements of BS EN 845: Part 1, at every third course. E/4- If the wall height is more than 3.5 m, galvanized beam-masonry wall ties of 2.5 mm x 20 mm x 75 mm, complying with the requirements of BS EN 845: Part 1, shall be fixed at 1.2 m c/c approximately. E/5- Concrete stiffeners should be provided around windows and doors openings to allow for stiffening the wall free ends. F- Condensation To avoid the condensation problem that is expected to happen in walls built with Sandwichblocks, special coatings that have very low water-vapor permeability characteristic shall be applied on the external surface of the walls. 7 Issue Date 19/12/2004
11 G- Publications referred to: BS 1881: Part 124 BS 4027 BS 6073: Part 1 BS 6073: Part 2 BS EN 197: Part 1 BS EN 845: Part 1 BS EN 934: Part 2 BS EN 1008 BS EN 1602 BS EN 1934 BS EN 11925: Part 2 BS EN Method for analysis of hardened concrete Specification for sulfate-resisting Portland cement Specification for precast concrete masonry units Method for specifying precast concrete masonry units Cement Part 1: Composition, specifications and conformity criteria for common cements Specification for ancillary components for masonry Part 1: Ties, tension straps, hangers and brackets Admixtures for concrete, mortar and grout Part 2: Concrete admixtures Definitions, requirements, conformity, marking and labeling Mixing water for concrete Thermal insulation products for building applications determination of apparent density Thermal Performance of Buildings - Determination of Thermal Resistance by Hot Box Method Using Heat Flow Meter - Masonry Reaction to fire tests Ignitability of building products subjected to direct impingement of flame Part 2: Single flame source test Aggregates for concrete BS EN Thermal performance of building materials and products Determination of thermal resistance by means of guarded hot plate and heat flow meter methods dry and moist products of medium and low thermal resistance BS EN Thermal performance of building materials and products Determination of thermal resistance by means of guarded hot plate and heat flow meter methods products of high and medium thermal resistance BS EN ISO 6946 BS EN ISO BS EN ISO 8990 Building components and building elements Thermal resistance and thermal transmittance Calculation method Building materials and products Procedures for determining declared design thermal values Thermal insulation Determination of steady-state thermal transmission properties Calibrated and guarded hot box 8 Issue Date 19/12/2004
12 ASTM C 518 ASTM C 1363 ASTM D 2863 Standard Test Method for Steady-State Thermal Transmission Properties by Means of the Heat Flow Meter Apparatus Standard Test Method for the Thermal Performance of Building Assemblies by Means of a Hot Box Apparatus Standard Test Method for Measuring the Minimum Oxygen Concentration to Support Candle-Like Combustion of Plastics (Oxygen Index) 9 Issue Date 19/12/2004
EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS
EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS 1. SCOPE 1.1 This specification covers the type, physical properties and dimensions of Expanded Polystyrene Insulation Board intended for use
Understanding BS EN 771-3: Aggregate concrete masonry units
60 Charles Street, Leicester LE1 1FB Tel: 0116 253 6161 Fax: 0116 251 4568 Email: [email protected] Website: www.cba-blocks.org.uk February 2006 Understanding BS EN 771-3: Aggregate concrete
CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011
CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS
Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in
REV 1-12.12.11/TB002 Technical Bulletin Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in conjunction with TRADA Technology and is intended to provide the reader with introductory
Annex of the certificate (Page 1/6) Accreditation Scope
As a Testing Laboratory Annex of the certificate (Page 1/6) Accreditation Scope Address: Küçük Çiğli Mh. 8780/1 Sk. No:5 Çiğli 35681 İZMİR / TÜRKİYE Phone : 0 232 376 24 25 Fax : 0 232 386 33 98 E-Mail
European Technical Approval ETA 13/0526
European Technical Approval ETA 13/0526 Trade Name Holder of the approval Website Generic type and use of construction product DOLCEA i3 PCIM S.A. Rue du Péquet 54 5590 Achene (Ciney) Belgium www.isoproc.eu
THERMAL INSULATION MATERIALS TEST METHOD SELECTION LIST
THERMAL INSULATION MATERIALS TEST METHOD SELECTION LIST Instruction: Check each test method for which you are requesting accreditation. An asterisk beside the NVLAP Test Method Code indicates that proficiency
Treatment of a surface or structure to resist the passage of water in the absence of hydrostatic pressure. presence of hydrostatic pressure.
Recommend Approval: Team Leader Date Division Chief Date Approved: Director Date Maryland Department of Transportation State Highway Administration Office of Materials Technology MARYLAND STANDARD METHOD
NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)
NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology CONCRETE MASONRY FOUNDATION WALL DETAILS TEK 5-3A Details (2003) Keywords:
Mandate M/116 MASONRY AND RELATED PRODUCTS
Mandate M/116 Page 1 sur 19 Mandate M/116 MANDATE TO CEN/CENELEC CONCERNING THE EXECUTION OF STANDARDISATION WORK FOR HARMONIZED STANDARDS ON CReatE MASONR AND RELATED PRODUCTS RELATED TO THE FOLLOWING
Loss Prevention Standard
Loss Prevention Standard LPS 1581: Issue 2.1 Requirements and tests for LPCB approval of nonload This Loss Prevention Standard is the property of BRE Global Ltd. and is made publicly available for information
07 21 19 Guide Specification STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
07 21 19 STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM 7819 Broadview Road Cleveland, OH 44131 800-522-4522 February, 2011 SPEC NOTE: This guide specification is intended for use when specifying
SECTION 03400 PRECAST CONCRETE STRUCTURES
SECTION 03400 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes specifications for precast concrete structures, including fabrication and erection. 1.02 REFERENCE STANDARDS A. American Society for
TECHNICAL SPECIFICATION SERIES 8000 PRECAST CONCRETE
TECHNICAL SPECIFICATION SERIES 8000 PRECAST CONCRETE TECHNICAL SPECIFICATION PART 8000 - PRECAST CONCRETE TABLE OF CONTENTS Item Number Page 8100 PRECAST CONCRETE CONSTRUCTION - GENERAL 8-3 8101 General
INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP
INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES Interpretations of the FTP CONTENTS FTP1 Adhesives used in A or B class divisions (FTP Code 3.1, Res A.754 para. 3.2.3) June 2000 FTP2 Pipe and duct
Construction Materials Testing. Classes of Test
Construction Materials Testing Classes of Test February 2014 Copyright National Association of Testing Authorities, Australia 2014 This publication is protected by copyright under the Commonwealth of Australia
Composite Panel Firewall Systems
Composite Panel Firewall Systems part of the Protecting more than your business Insulated mineral fibre panels have excellent thermal and acoustic properties, ideal for factory and office partition walls.
Section 5.0. Basements. Wall insulated externally. Wall insulated internally. Ba02. Product: Polyfoam ECO Floorboard Ba01.
Section 5.0 Basements Wall insulated externally Product: Polyfoam ECO Ba01 Wall insulated internally Product: Polyfoam ECO Ba02 Basements Basements Basement design Waterproofing BS 8102: 2009 Code of practice
Detailing of Reinforcment in Concrete Structures
Chapter 8 Detailing of Reinforcment in Concrete Structures 8.1 Scope Provisions of Sec. 8.1 and 8.2 of Chapter 8 shall apply for detailing of reinforcement in reinforced concrete members, in general. For
Guide for SOLID CONCRETE BLOCK SEALS
Guide for SOLID CONCRETE BLOCK SEALS July, 2006 Mine Safety and Health Administration SOLID CONCRETE BLOCK SEAL Formersection 30 CFR 75.335(a)(1) specifies requirements for seals constructed using solid
Introduction. Facade Fire Test on PUR External Thermal Insulation Composite System (ETICS)
1 Facade Fire Test on PUR External Thermal Insulation Composite System (ETICS) Introduction The new harmonised system for the classification of reaction to fire in EU member states is using the SBI test
Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high.
CI/SfB Tn6 L6813 September 2013 RIW CAVITY DRAIN R20 R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high. Other systems are available for specific uses,
cement Masonry Cement Engineered for quality and reliability, Lafarge cements for masonry deliver consistent performance. page 2 Lafarge Cement
cement Masonry Cement Engineered for quality and reliability, Lafarge cements for masonry deliver consistent performance. page 2 Lafarge Cement Lafarge in North America The Lafarge Group is the world leader
Mold Preventing I nterior System
interior insulation and renovation boards A system of components that have been designed to work perfectly together to repair damage caused by mold. The system consists of boards, insulation wedges, reveal
European technical approval
Authorised and notified according to Article 10 of the Council Directive 89/ 106/EEC of 21 December 1988 on the approximation of laws, regulations and administrative provisions of Member States relating
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry
SPECIFICATION Section 03450 - Insulated Precast Concrete Wall Panels
Lafarge/CPCI Guide Specification SPECIFICATION Section 03450 - Insulated Precast Concrete Wall Panels 1.0 General 1.1 Description.1 The General conditions of the Contract and Supplementary General Conditions
Built to Last. Built for Beauty. Good. Solid. Logix. TM
Built to Last. Built for Beauty. Good. Solid. Logix. TM Quality, Value and Service Introducing LOGIX Insulated Concrete Forms. Based on the simple concept of interlocking blocks, LOGIX ICF gives you a
GRADATION OF AGGREGATE FOR CONCRETE BLOCK
GRADATION OF AGGREGATE FOR CONCRETE BLOCK Although numerous papers have been written concerning the proper gradation for concrete mixes, they have generally dealt with plastic mixes, and very little published
How To Test For Premer Retardant
TEST REPORT NEBS COMPLIANCE CHOMERICS PREMIER CONDUCTIVE PLASTIC Prepared by: CHOMERICS R&D 84 DRAGON COURT WOBURN, MA 01801 Test Report Number: TR 1007 EN 0206 Chomerics Approved Signatory: This report
CHESTERFLEX ROOF WATERPROOFING MEMBRANES
CI/SfB (47) Ln2 Chesterfelt Ltd CHESTERFLEX ROOF WATERPROOFING MEMBRANES Certificate No 94/3062 DETAIL SHEET 2 Product THIS DETAIL SHEET RELATES TO CHESTERFLEX ROOF WATERPROOFING MEMBRANES, POLYESTER REINFORCED
SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701)
SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701) 55-1 GENERAL The Contractor shall perform all work required by the plans for construction of pipe for storm drains, precast polymer trench drains
SPECIAL COMPOUND FOR RHEOPLASTIC AND ANTI-CORROSION SUPERCONCRETE WITH VERY HIGH DURABILITY
BS 40 M6 MuCis mono SPECIAL COMPOUND FOR RHEOPLASTIC AND ANTI-CORROSION SUPERCONCRETE WITH VERY HIGH DURABILITY LE CE LE type: "expansive binder which allows the production of extremely fluid concrete
Design and Construction of Cantilevered Reinforced Concrete Structures
Buildings Department Practice Note for Authorized Persons, Registered Structural Engineers and Registered Geotechnical Engineers APP-68 Design and Construction of Cantilevered Reinforced Concrete Structures
GigaCrete Specification PlasterMax
GigaCrete Inc. 6775 Speedway Blvd. Suite M105 Las Vegas, NV 89115 Ph (702) 643-6363 Fax (702) 643 1453 www.gigacrete.com GigaCrete Specification PlasterMax PlasterMax : Fire Rated Plaster for Direct Application
FERMACELL Powerpanel H 2 O for Wet & Moisture affected areas
FERMACELL Powerpanel H 2 O for Wet & Moisture affected areas Powerpanel H 2 O is a cement based board from FERMACELL. Board Characteristics Board Thickness 12.5 mm Board Sizes 1000 x 1200 mm 50 sheets/pallet
18 June 2001 GUIDELINES ON FIRE TEST PROCEDURES FOR ACCEPTANCE OF FIRE-RETARDANT MATERIALS FOR THE CONSTRUCTION OF LIFEBOATS
INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR Telephone: 020 7735 7611 Fax: 020 7587 3210 Telex: 23588 IMOLDN G IMO E Ref. T4/4.01 MSC/Circ.1006 18 June 2001 GUIDELINES ON FIRE
Tex-421-A, Splitting Tensile Strength of Cylindrical Concrete Specimens
Contents: Section 1 Overview...2 Section 2 Apparatus...3 Section 3 Test Specimens...4 Section 4 Procedure...5 Texas Department of Transportation 1 08/99 06/08 Section 1 Overview Effective dates: August
ROXUL Board Insulation Section 07 21 13 Master Guide Specification (CAVITYROCK ) Page 1 April 2016
Master Guide Specification (CAVITYROCK ) Page 1 Click on the pilcrow in the MS Word Toolbar to toggle ROXUL GUIDE NOTES on and off. Delete this text before incorporating the section into a Project Manual.
NAPCA BULLETIN 18-99 APPLICATION PROCEDURES FOR CONCRETE WEIGHT COATING APPLIED BY THE COMPRESSION METHOD TO STEEL PIPE
NAPCA BULLETIN 18-99 APPLICATION PROCEDURES FOR CONCRETE WEIGHT COATING APPLIED BY THE COMPRESSION METHOD TO STEEL PIPE GENERAL a. These specifications may be used in whole or in part by any party without
Tremco Fire Protection Systems Group Technical Bulletin
Compartmentalization products and design play a key role in protecting lives and property from fire. Understanding the tools and techniques available for firestopping is of utmost importance to designers,
) and air spaces (R a
5.3.3 Thermal Resistance (R-value) Common thermal properties of materials and air spaces are based on steady state tests, which measure the heat that passes from the warm side to the cool side of the test
R-VALUES AND U-FACTORS OF SINGLE WYTHE CONCRETE MASONRY WALLS. TEK 6-2B Energy & IAQ (2009) Related TEK: 6-1B, 6-11, 6-12C INTRODUCTION
An information series from the national authority on concrete masonry technology R-VALUES AND U-FACTORS OF SINGLE WYTHE CONCRETE MASONRY WALLS TEK 6-2B Energy & IAQ (2009) INTRODUCTION Single wythe concrete
Asphalt Shingle Application Requirements
Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt
SECTION 02630 STORM DRAINAGE SYSTEM
SECTION 02630 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes specifications for storm drainage systems including modifications and connections to existing storm drainage systems. 1.02 REFERENCE
CORROSION ENGINEERING RESIN-BASED POLYMER CONCRETES AND GROUTS
AN ERGONARMOR COMPANY TECHNICAL INFORMATION SPECIFICATION FOR INSTALLATION 07/11 SUPERSEDES 04/00 PAGE 1 OF 6 CORROSION ENGINEERING RESIN-BASED POLYMER CONCRETES AND GROUTS 1. SCOPE 1.1 This specification
LAYING BLOCK AND BRICK
LAYING BLOCK AND BRICK Products highlighted in this section: SAKRETE Type N Mortar Mix SAKRETE Type S Mortar Mix Brick And Block Laying Basics The first step in building a brick or block wall is to construct
Construction. 3-part thixotropic epoxy patching mortar. Product Description. Tests
Product Data Sheet Edition 05/12/2014 Identification no: 020204030010000044 Sikadur -41 CF Rapid 3-part thixotropic epoxy patching mortar Construction Product Description Uses Characteristics / Advantages
ETAG 004 EXTERNAL THERMAL INSULATION COMPOSITE SYSTEMS WITH RENDERING
European Organisation for Technical Approvals Europäische Organisation für Technische Zulassungen Organisation Européenne pour l Agrément Technique Edition March 2000 Amendment June 2008 GUIDELINE FOR
Fiberglas, Exterior Wall Thermal Insulation
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
R-VALUES AND U-FACTORS OF SINGLE WYTHE CONCRETE MASONRY WALLS. TEK 6-2C Energy & IAQ (2013) Related TEK: 2-5B, 6-1C, 6-4B, 6-11A, 6-12C, 6-12D, 6-12E
An information series from the national authority on concrete masonry technology R-VALUES AND U-FACTORS OF SINGLE WYTHE CONCRETE MASONRY WALLS TEK 6-2C Energy & IAQ (201) INTRODUCTION Single wythe concrete
EXPERT OPINION on the applicability of the construction technology "GRÈMOUND non-tectonic system on grounds of the documentation submitted
ÉMI Építésügyi Minőségellenőrző Innovációs Nonprofit Kft. [ÉMI Non-Profit Limited Liability Company for Quality Control and Innovation in Building; ÉMI Non-Profit Ltd.] Address: 1113 Budapest, Diószegi
COMMERCIAL ITEM DESCRIPTION PACKAGING MATERIAL, SHEET
[METRIC] A-A-59135 28 OCTOBER 1997 SUPERSEDING PPP-C-1752D(3) 1 FEBRUARY 1993 COMMERCIAL ITEM DESCRIPTION PACKAGING MATERIAL, SHEET The General Services Administration has authorized the use of this commercial
Check-list for auditors. Audit visit at candidate registered laboratories
Check-list for auditors Audit visit at candidate registered laboratories 1 Contents Introduction Laboratory documentation required by the standard(s), available for inspection by the auditor Items to be
SPECIFICATIONS. INTERLOCKING CONCRETE POROUS PAVING UNITS or Permeable Interlocking Concrete Pavers (PICP)
SPECIFICATIONS INTERLOCKING CONCRETE POROUS PAVING UNITS or Permeable Interlocking Concrete Pavers (PICP) Part 1 General 1.1 CONFORMITY Conforms to the requirements of the general conditions of the contract.
7. Installation. installation 7.1.1. CAST-IN WINDOW SYSTEM 7.1. INSTALLATION OF WINDOW MAIN FRAME
7. Installation Window involves the fixing of window frame at an earlier construction stage and subsequent of the window sashes. This is a highly workmanship dependent process. Only trained and approved
European Organisation for Technical Approvals
Warrington Certification Limited, Holmesfield Road, Warrington, WA1 2DS Tel. +44 (0) 1925-646777 Fax +44 (0) 1925-646667 Member of EOTA Authorised and notified according to Article 10 of the Council Directive
Fire Resistance of Brick Masonry
TECHNICAL NOTES on Brick Construction 1850 Centennial Park Drive, Reston, Virginia 20191 www.gobrick.com 703-620-0010 Fire Resistance of Brick Masonry 16 March 2008 Abstract: This Technical Note presents
1/9/2013. Terminology Calculating Heat Transfer Code Requirements Design Examples and Sustainability
1/9/13 By Brett T. Fagan, P.E. Presented by Marie Horan, P.E. Building Diagnostics, Inc. Building Diagnostics Terminology Calculating Heat Transfer Code Requirements Design Examples and Sustainability
HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS
BSW HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS BSW is a fully reinforced Pre-Applied system membrane designed for horizontal and vertical external blind-side
COMPACTING BITUMINOUS SPECIMENS USING THE SUPERPAVE GYRATORY COMPACTOR (SGC)
Test Procedure for COMPACTING BITUMINOUS SPECIMENS USING THE SUPERPAVE TxDOT Designation: Tex-241-F Effective Date: December 2015 1. SCOPE 1.1 Use this test method to: compact cylindrical specimens of
Knauf Aquapanel Interior. Tile Backing. Cement board for wet areas. Will not deteriorate in water. Easy to score and snap
Tile Backing Will not deteriorate in water Easy to score and snap Resistant to mould and mildew Knauf Aquapanel Interior Cement board for wet areas Knauf Aquapanel Interior Cement Board Drywall for Wet
SECTION 07 21 16 - PRE-ENGINEERED BUILDING BLANKET INSULATION
PROJECT ARCHITECT RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
Insulated Roof & Wall Panels. Product Data Sheet. Trapezoidal Insulated Roof Panels KS1000 RW
Insulated Roof & Wall Panels Trapezoidal Insulated Roof Panels KS1000 RW Overview Kingspan roof panel systems present a superior system compared to conventional multi-part site assembled systems. They
CCU Engineering Specifications. Section 003300 PRECAST CONCRETE PRODUCTS
CCU Engineering Specifications Section 003300 Effective Date: Nov. 1st, 2011 Page 1 of 5 PRECAST CONCRETE PRODUCTS PART 1 - GENERAL The following specification is intended for use for the design, selection
www.klmtechgroup.com TABLE OF CONTENT
Page : 1 of 31 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 2 REFERENCES
European Technical Approval ETA 13/0384
European Technical Approval ETA 13/0384 Trade Name Holder of the approval Website Generic type and use of construction product Isobriq EU, Isobriq LE, Isobriq PA & Isobriq ZE Isobriq sa 49 Rue Slar 4801
Simplifying design and construction. Alan Tovey, Director The Basement Information Centre
Simplifying design and construction Alan Tovey, Director The Basement Information Centre Simplifying design and construction Grades of construction Construction options Design and waterproofing issues
COMMONLY USED RESIDENTIAL BUILDING CODES
COMMONLY USED RESIDENTIAL BUILDING CODES INTERNATIONAL RESIDENTIAL CODE (2009) form revised 5/10 FOUNDATION 1. DESIGN OF FORMWORK. Section 1906.1 IBC 2009, Section R404.1.2.3.6 IRC 2009, ACI 318 Section
1997 Uniform Administrative Code Amendment for Earthen Material and Straw Bale Structures Tucson/Pima County, Arizona
for Earthen Material and Straw Bale Structures SECTION 70 - GENERAL "APPENDIX CHAPTER 7 - EARTHEN MATERIAL STRUCTURES 70. Purpose. The purpose of this chapter is to establish minimum standards of safety
GYPSUM BOARD, GYPSUM PANEL PRODUCTS AND PLASTER
CHAPTER 25 GYPSUM BOARD, GYPSUM PANEL PRODUCTS AND PLASTER User note: Code change proposals to this chapter will be considered by the IBC Structural Code Development Committee during the 2016 (Group B)
Example Specification for Concrete using Current Building Code Requirements
Example Specification for Concrete using Current Building Code Requirements DISCLAIMER: This specification is an example that accompanies a seminar titled The P2P Initiative: Performance-based Specs for
Effect of basalt aggregates and plasticizer on the compressive strength of concrete
International Journal of Engineering & Technology, 4 (4) (2015) 520-525 www.sciencepubco.com/index.php/ijet Science Publishing Corporation doi: 10.14419/ijet.v4i4.4932 Research Paper Effect of basalt aggregates
FederalDemocratic RepublicofEthiopia
FederalDemocratic RepublicofEthiopia EDICTOFGOVERNMENT± Inordertopromotepubliceducationandpublicsafety, equaljusticeforal,abeterinformedcitizenry,therule oflaw,worldtradeandworldpeace,thislegaldocumentis
WATERPROOFING FOR CONCRETE STRUCTURES
MANUAL OF CONTRACT DOCUMENTS FOR ROAD WORKS VOLUME 1 SPECIFICATION FOR ROAD WORKS SERIES 2000 WATERPROOFING FOR CONCRETE STRUCTURES Contents Clause Title Page 2001 General 2 2002 Protection of Bridge Deck
FLAMMABILITY REQUIREMENTS FOR 25.853-1 AIRCRAFT SEAT CUSHIONS
FLAMMABILITY REQUIREMENTS FOR 25.853-1 AIRCRAFT SEAT CUSHIONS ANM-110 1. PURPOSE. This Advisory Circular (AC) provides guidance material for demonstrating compliance with the Federal Aviation Regulations
TARIFF CODE and updates standard
TARIFF CODE and updates standard No HS CODE AHTN CODE PRODUCT DESCRIPTION PRODUCT TYPE STANDARDS IDENTIFIED 7207 Semi finished products of iron or non alloy steel Containing by weight less than 0.25% of
English version. Raised access floors
EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM EN 12825 August 2001 ICS 91.060.30 English version Raised access floors Planchers surélevés Doppelböden This European Standard was approved by CEN on
necessary for years of satisfactory service. SmartBlock insulating form concrete walls share the
Chapter 7 PLUMBING AND ELECTRICAL 7.1 Introduction to Plumbing and Electrical Consideration of support services such as plumbing and electrical systems from the preliminary schematics phase through final
STANDARD SPECIFICATION. for. Plumbing, Heating, Hot Water, Cold Water & Electrical work. Sussex Lodge London W2 & 16 Stanhope Terrace London W2
STANDARD for Plumbing, Heating, Hot Water, Cold Water & Electrical work undertaken by owners within the building known as Sussex Lodge London W2 & 16 Stanhope Terrace London W2 BPME Consulting Engineers
Steel-framed Walls. Insulation
Insulation A4/8 SF AW1192 Issue 4 Nov 2012 Steel-framed Walls Insulation guide Helps achieve a 6-star house energy rating Rigid and flexible Kingspan AIR-CELL solutions available Vapour barrier or vapourpermeable
Technical Notes 3B - Brick Masonry Section Properties May 1993
Technical Notes 3B - Brick Masonry Section Properties May 1993 Abstract: This Technical Notes is a design aid for the Building Code Requirements for Masonry Structures (ACI 530/ASCE 5/TMS 402-92) and Specifications
Precast Concrete Insulated Sandwich Wall Panels
Precast Concrete Insulated Sandwich Wall Panels Technical Brochure Canadian Precast/Prestressed Concrete Institute Precast Concrete Insulated Sandwich Wall Panels Insulated precast concrete panels provide
B. ASTM C 533 Calcium Silicate Block and Pipe Thermal Insulation. C. ASTM C 547 Mineral Fiber Preformed Insulation
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
4 Installation Requirements
4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming
Excerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
Light-Weight Panels. High quality panels. www.stenca.com
Light-Weight Panels High quality panels WELCOME TO STENCA TRADING - Global focus with local service Stenca Trading offers optimal solutions for the offshore, marine, refineries and cogeneration industry.
ENGINEERING SPECIFICATION PULTRUDED DYNARAIL FIBERGLASS LADDER & LADDER CAGES
ENGINEERING SPECIFICATION PULTRUDED DYNARAIL FIBERGLASS LADDER & LADDER CAGES PART 1 - GENERAL 1.1 SCOPE OF WORK SECTION 06610 FIBERGLASS REINFORCED PLASTICS (FRP) FABRICATIONS PULTRUDED SQUARE TUBE LADDER
DESIGN OF SLABS. 3) Based on support or boundary condition: Simply supported, Cantilever slab,
DESIGN OF SLABS Dr. G. P. Chandradhara Professor of Civil Engineering S. J. College of Engineering Mysore 1. GENERAL A slab is a flat two dimensional planar structural element having thickness small compared
FLOORS REINFORCEMENT Shear Stud Connector for steel- concrete composite structures cold applied by pins
www.tecnaria.com FLOORS REINFORCEMENT Shear Stud Connector for steel concrete composite structures cold applied by pins HIGHPERFORMANCE FLOORS COMPOSITE STEEL AND CONCRETE STRUCTURES: STATIC AND ECONOMIC
Roxul Board Insulation Section 07 21 13 Master Guide Specification (CAVITYROCK DD) Page 1 October 2013
Master Guide Specification (CAVITYROCK DD) Page 1 ROXUL GUIDE NOTE: This master specification section is based on ROXUL INC., CAVITYROCK DD. Standard application: Cavity wall. ROXUL GUIDE NOTE: This master
PRESENTATION ON REPAIR AND REHABILITATION OF BUILDINGS DAMAGED IN EARTHQUAKE. By H P Gupta & D K Gupta
PRESENTATION ON REPAIR AND REHABILITATION OF BUILDINGS DAMAGED IN EARTHQUAKE By H P Gupta & D K Gupta DIFFERENT TYPES OF DAMAGES 1.Minor cracks 0.5 to 5 mm wide in load or non-load bearing walls 2.Major
Chapter 3 Pre-Installation, Foundations and Piers
Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory
Monocouche Best Practice Guide. New-Build Housing Managing movement to avoid cracking
Monocouche Best Practice Guide New-Build Housing Managing movement to avoid cracking Avoiding Cracking For The Designer Visible cracks in render are unsightly and although not hazardous to the construction
Laying the First Course. 1. Excavate the site and construct the footing.
Use QUIKRETE Mortar Mix or Mason Mix lay up a concrete block wall as shown. QUIKRETE Mortar Mix or Mason Mix Concrete block Mason's line Line blocks 4' level brick trowel Jointer Mason's hammer Stiff brush
CONTRACT SPECIFICATIONS - SEISMIC ISOLATION BEARINGS
CONTRACT SPECIFICATIONS - SEISMIC ISOLATION BEARINGS 1.0 DESIGN 1.1 Scope of Work 1.1.1 This work shall consist of furnishing Isolation Bearings and installing Isolation Bearing Assemblies at the locations
1.5 Concrete (Part I)
1.5 Concrete (Part I) This section covers the following topics. Constituents of Concrete Properties of Hardened Concrete (Part I) 1.5.1 Constituents of Concrete Introduction Concrete is a composite material
Master Panel 1000 W Wall
Master Panel 1000 W Wall Product Description In order to generate an aesthethic outlook wall panels are generally produced as micro hedge. Besides, in connection points concealed screw is used which provides
SERIES NG 1800 STRUCTURAL STEELWORK
MANUAL OF CONTRACT DOCUMENTS FOR HIGHWAY WORKS VOLUME 2 NOTES FOR GUIDANCE ON THE SPECIFICATION FOR HIGHWAY WORKS SERIES NG 1800 STRUCTURAL STEELWORK Contents Clause Title Page NG 1800 (08/14) General
