Variable-Speed Fan Retrofits for Computer-Room Air Conditioners
|
|
|
- Damian Hopkins
- 10 years ago
- Views:
Transcription
1 Variable-Speed Fan Retrofits for Computer-Room Air Conditioners Prepared for the U.S. Department of Energy Federal Energy Management Program Technology Case Study Bulletin By Lawrence Berkeley National Laboratory Steve Greenberg September 2013
2 Contacts Steve Greenberg Lawrence Berkeley National Laboratory One Cyclotron Road, 90R3111 Berkeley, California (510) For more information on FEMP, please contact: Will Lintner, P.E., CEM Federal Energy Management Program U.S. Department of Energy 1000 Independence Ave. S.W. Washington, D. C (202)
3 Acknowledgements EPRI: Dennis Symanski, Brian Fortenbery Synapsense: Garret Smith, Patricia Nealon Vigilent: Corinne Vita NetApp: Ralph Renne LBNL: Ed Ritenour, Mike Magstadt, William Tschudi 3
4 Table of Contents 1 Executive Summary Introduction The Opportunity Steps for implementing a variable-speed drive fan retrofit Install variable-speed drives Install monitoring and control system Start-up, Test, and Commission the System Results Energy savings potential Effect on operations Conclusion References
5 1 Executive Summary The purpose of this case study is to provide concepts for more cost-effective cooling solutions in data centers, while keeping in mind that the reliability of computing systems and their respective cooling systems is always a key criterion. This case study documents three retrofits to existing constant-speed fans in computer-room air conditioners (CRACs), all located in California: first, a forty year-old, 6,000 ft 2 data center located at the Lawrence Berkeley National Laboratory (LBNL) in Berkeley, with down-flow, water-cooled CRACs; second, a three year-old, 1,000 ft 2 data center owned by NetApp in Sunnyvale, with up-flow, water-cooled units; and, third, a twelve year-old, 1300 ft 2 data center owned by the Electric Power Research Institute (EPRI) in Palo Alto, with down-flow, air-cooled units. Prior to these retrofits, it was widely assumed that conventional CRACs with reciprocating compressors and direct-expansion cooling coils needed to operate with constant fan speed, in order to keep the coils from freezing and other operational reasons. Case studies of retrofitted variable-speed controls in three data centers, using two different vendors of wireless controls, demonstrated that variable speed operation is not only possible, but results in significant energy savings and equal or improved cooling and reliability. The range of cooling system energy use reduction was 22-32% when compared to the constant-speed fan case. These systems, including the monitoring and controls needed for proper operation, have simple payback periods under two years. 2 Introduction This case study is one in a series created by the Lawrence Berkeley National Laboratory (LBNL) for the Federal Energy Management Program (FEMP), a program of the U.S. Department of Energy. Geared towards engineers and data center Information Technology (IT) and facility managers, this case study provides information about technologies and practices to use in operating and retrofitting existing data centers for sustainability. This case study documents three retrofits to existing constant-speed fans in computer-room air conditioners (CRACs), all located in California: first, a forty year-old, 6,000 ft 2 data center located at LBNL with down-flow, water-cooled CRACs; second, a three year-old, 1,000 ft 2 data center owned by NetApp in Sunnyvale, with up-flow, water-cooled units; and, third, a twelve year-old, 1300 ft 2 data center owned by the Electric Power Research Institute (EPRI) in Palo Alto, with down-flow, air-cooled units. The purpose of this case study is to provide concepts for more cost-effective cooling solutions, while keeping in mind that the reliability of computing systems and their respective cooling systems is always a key criterion. 5
6 3 The Opportunity Computer room air conditioners (CRACs) are often used to provide cooling to the Information Technology (IT) loads, especially in legacy data centers. CRACs use a vapor-compression refrigeration cycle to remove heat from the data center air, and pump it either into water (in turn cooled by a cooling tower or a dry cooler located outdoors) or directly into the outdoor air with a remote condenser with fan. While the compressors in the CRAC units are the largest energy consumer of the cooling system, the fans located in the CRACs (used to circulate room air through the units cooling coils) are also large energy users. CRACs were historically designed to operate at one fan speed even though many units have multiple (up to 4) stages of cooling; this scheme simplifies the internal controls of the CRAC (the risk of freezing is minimized and overall CRAC control stability is made easier) but running the fans at full speed even at reduced cooling loads wastes energy. CRAC fan systems generally follow the fan laws, i.e. the power required by the fan is proportional to the cube of the fan speed. If the efficiencies of the fan, motor, and belt drive all remain constant, the electrical input power will scale the same way. For example, if a fan requires 6.5 kw at 100% speed, it will require only 3.3 kw at 80% speed, since is 0.51 (see Figure 1). Not only will the fan power be reduced, but since the fan power all becomes heat in the space and must be removed by the cooling system, there are significant secondary savings in the compressors and heat rejection system as well. Figure 1. Fan power as a function of speed (the cube law ). (Credit: Smith, 2013) It should be noted that computer-room air handlers (CRAHs) which have a filter, cooling coil using chilled water, and a fan are not the subject of this case study. However, because they do not have the same operational constraints that CRACs have, CRAHs typically have even better savings potential from fan speed control retrofits. See Coles et al, 2012 for a case study on CRAH retrofits; note also the retrofit included replacing the fans themselves with more-efficient plenum fans for additional savings, a retrofit that would apply equally well to CRACs. 6
7 While there are no retrofit kits available (from the original manufacturer) for the CRACs with reciprocating compressors that were the subject of this study, CRACs with scroll compressors are available with VSD fans, and there also are factory retrofit kits for these more recent CRACs. Maintenance for the fan components (bearings, motors, belts and sheaves) is also required, so operating them at reduced speed results in less wear and thus additional operational cost savings. 4 Steps for implementing a variable-speed drive fan retrofit These demonstrations show that existing CRAC fans can be successfully retrofitted with variable-speed drives. There are common steps that each of the three projects took, and other steps were applied on a case-by-case basis. 4.1 Install variable-speed drives A variable-speed drive (VSD) was added to the wiring to the fan motor of each CRAC. VSDs, also known as variable-frequency drives (VFDs), are commodity power electronic devices, commonly used for HVAC fans and pumps and numerous industrial applications. They work by converting the incoming 60 Hz alternating current (AC) power supplied by the utility to direct current and then, in the inverter section, creating a variable-frequency, variable-voltage AC output that is used to operate the motor at variable speed. Existing standard-efficiency AC induction motors can be used (as was the case at NetApp and EPRI), while upgrading to premium-efficiency motors will increase reliability and save additional energy as well (LBNL replaced their CRAC motors). Newer motors have insulation systems that are more resistant to degradation from the voltage spikes produced by VSDs, so they will be more durable than older motors, though if the VSD is kept close to the motor (as was the case in all three retrofits), this potential problem is minimized. VSDs can be used in their basic form (without a bypass; the motor can only operate through the VSD) as was done at LBNL and NetApp, or with a bypass (the motor can also be operated at full speed with the VSD out of the circuit). See Figures 2 and 3. Bypasses enable extra redundancy, in that if the VSD fails, the motor can still be operated, but the bypass adds size and extra cost. Since there are several other single points of failure in typical fan applications, many VSD installations are done with basic drives. The VSD can be mounted inside the CRAC, with deference to condensate dripping off the cooling coil (Figure 2), on a nearby wall or column (Figure 3), or under the floor (Figure 4). 7
8 Figure 2. VSD installation: plain VSD mounted inside the CRAC (Credit: Symanski, 2012). 8
9 Figure 3. VSD installation: VSD with bypass mounted on wall near the CRAC (Credit: Symanski 2012). Figure 4. VSD installation: plain VSD mounted under the floor near the CRAC (Credit: Ritenour, 2012) 9
10 4.2 Install monitoring and control system Since the CRAC internal controls did not include fan speed, an external controller was needed. While completely hard-wired control systems exist from a variety of vendors, the installation cost in an existing center is high relative to wireless options. In addition, wireless sensor vendors already have data-center monitoring systems available, and their fan control options are a relatively easy addition to a monitoring scheme. See DOE 2010 for a discussion of wireless sensor systems. In the EPRI case, a Vigilent system provided full monitoring and control. In the NetApp case, a Vigilent system provided monitoring and interfaced with the in-house Automatic Logic Corporation (ALC) system for VSD control. In the LBNL case, a Synapsense system provided full monitoring and control. Monitoring of supply and return temperatures was included with all systems, but they used the CRACs internal controls for temperature control, i.e. ramping up and down the staging of the CRAC cooling systems. The control system needs to monitor temperatures in the data center space to ensure that the IT cooling loads are met at no higher than the required inlet temperature. Typically an interface between the CRAC controls and the external controller is appropriate in order for the fan speed control to monitor conditions in the CRAC, which can also allow resetting of the temperature control setpoint of the internal CRAC controller. The Synapsense system included additional temperature sensors added to the CRAC s evaporator and condenser to ensure that the refrigerant compressor suction pressure doesn t go too low or that the compressor discharge pressure doesn t go too high. Since the pressure and temperature are not independent in the evaporator, and likewise in the condenser, temperatures (easily measured with clamp-on sensors) are used as proxies for the pressures. The Vigilent system included an additional temperature sensor for each CRAC s evaporator. Both systems ramp up fan speeds as needed to prevent the coil temperature from getting so low as to risk freeze-up. 4.3 Start-up, test, and commission the system As with any new equipment, the VSDs and their controls need to be programmed, started, tested, and commissioned to make sure they operate according to a sequence of operation, including the full range of load under normal operation, and under identified fault conditions to make sure that appropriate action is taken to protect equipment and send alarms to operators and maintenance personnel as appropriate. One issue that was common was condensation within the CRACs. Typically, these units operate with wet evaporator (cooling) coils, which mean condensation is dripping off the coils, and should be taken care of with the internal drip pan and drainage. At LBNL, it was noted that there was some carry-over of water into the air stream; this was a reason for locating the VSD outside of the CRAC. 10
11 5 Results Results from the three retrofits are described below. In summary, all systems saved significant amounts of energy and provided equal or better cooling service. 5.1 Energy savings potential Variable-speed fan retrofits can significantly reduce energy consumption and improve power utilization effectiveness in data centers. The results of these retrofits show significant energy savings for each installation. A commonly-used metric for measuring the performance of data center infrastructure is Power Usage Effectiveness, or PUE, which is the ratio of the total energy used by the data center divided by the energy used by the IT equipment (Green Grid, 2012). Thus, the lower the PUE, the better, with a PUE of 1.0 the theoretical minimum assuming no energy overhead is used for cooling, power distribution or lighting; PUEs below 1.1 have been demonstrated, while values in the range of 1.5 to 2.0 are very common. Constituents of the PUE overhead can be expressed using fractional values; for example if the HVAC system uses 0.25 times as much energy as the IT equipment, the power distribution losses use 0.05 times the IT, and lighting uses 0.01 times the IT, adding these together results in a total overhead of 0.31 and thus a PUE of While PUE numbers are formally taken as whole-year ratios of energy, informally (and in this case study) ratios of power can also be used. At LBNL, the variable-speed fan controls caused a drop of 6 kw (159 to 153 kw) in the cooling power, even though the IT power increased by about 100 kw (353 to 454 kw) over the same period. This represents an improvement in the cooling overhead from 0.45 to 0.34, a 24% reduction in cooling power (Ritenour, 2012; Smith et al, 2013). The simple payback period for the system, including the monitoring and controls for the data center, was under 2 years (Nealon, 2013). At EPRI, the fan controls saved up to 19% including the fans and compressor power (located in the CRACs themselves), and 31% when the outdoor units were included. The outdoor units are refrigerant-to-air condenser coils with fans; the reduced heat rejection meant less condenser fan power, adding to the savings. The overhead of the cooling system (again, as a fraction of IT input power) was improved from 0.64 to (Symanski, 2012 and 2013). The simple payback period for the system, including the monitoring and controls for the data center, was under 2 years (Vita, 2013). At NetApp, results were nearly identical to those at EPRI. 5.2 Effect on operations The wireless monitoring systems greatly improved the ability to check the temperature control status of the data centers. Combined with the wireless or hybrid control of the airflow through the CRACs and thus to the IT loads, the service level is increased because the system can dynamically respond to meet the changing loads in a data center or to compensate for a malfunctioning CRAC. 11
12 At LBNL, the CRACs were manually operated with just the needed number ( N ) of units, which meant a failure needed to be manually responded to. With the automatic control system, N+1 units are now operated, typically with reduced fan speed, which improves the redundancy and reliability of the cooling system. 6 Conclusion Prior to these studies, it was widely assumed that conventional computer-room air conditioners with reciprocating compressors and direct-expansion cooling coils needed to operate with constant fan speed in order to keep the coils from freezing and for other operational reasons. Case studies of retrofitted variable-speed controls in three data centers, using two different vendors of wireless controls, demonstrated that not only is variable speed operation possible, but results in significant energy savings and equal or improved cooling and reliability. The range of cooling system energy use reduction was 22 to 32% when compared to the constant-speed fan case. These systems, including the monitoring and controls needed for proper operation, have simple payback periods under two years. 12
13 References Coles, H., S. Greenberg (Lawrence Berkeley National Laboratory) and C. Vita (Vigilent) "Demonstration of Intelligent Control and Fan Improvements in Computer Room Air Handlers", Berkeley, CA: Lawrence Berkeley National Laboratory. LBNL-6007e. November. Available at DOE, 2010, Wireless Sensors Improve Data Center Energy Efficiency. Technology Case Study Bulletin, September. Available at Green Grid, 2012, White Paper #49, PUE: A Comprehensive Examination of the Metric, V. Avelar et al, eds., Available at Nealon, 2013, personal communication from Patricia Nealon of Synapsense to Steve Greenberg, May 28. Ritenour, E. (Lawrence Berkeley National Laboratory), LBNL IT Computing Facilities Variable Speed CRACs: How Efficient is That!, presentation at the Silicon Valley Leadership Group Data Center Efficiency Summit, Sunnyvale, CA, October 24. Available at Smith, G., Inniss, D. (Synapsense) and S. Greenberg (Lawrence Berkeley National Laboratory), Navigating Tradeoffs between Reliability and Energy Efficiency: A Case Study of Automated CRAC Control in a Medium-Sized Legacy Data Center. In press. Symanski, D. (Electric Power Research Institute), Better Cooling With Slower CRAC Fans, presentation at the Silicon Valley Leadership Group Data Center Efficiency Summit, Sunnyvale, CA, October 24. Available at Symanski-Vigilent-WEBSITE.pdf Symanski, D. (Electric Power Research Institute), Data Center Power Quality and Energy Efficiency, presentation at the Moffett Park Power Quality Workshop, Sunnyvale, CA, January 23. Vita, 2013, personal communication from Corinne Vita of Vigilent to Steve Greenberg, June 3. 13
14 DOE/EE-0971 September 2013 Printed with a renewable-source ink on paper containing at least 50% wastepaper, including 10% post consumer waste.
Improving Data Center Efficiency with Rack or Row Cooling Devices:
Improving Data Center Efficiency with Rack or Row Cooling Devices: Results of Chill-Off 2 Comparative Testing Introduction In new data center designs, capacity provisioning for ever-higher power densities
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
Better Cooling With Slower CRAC Fans
Better Cooling With Slower CRAC Fans Dennis P. Symanski EPRI - Senior Project Manager SVLG Data Center Efficiency Summit 24OCT2012 AMD Sunnyvale, CA Thanks To The California Energy Commission!!! 2 EPRI
Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers
Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National
Drives and motors. A guide to using variable-speed drives and motors in data centres
Drives motors A guide to using variable-speed drives motors in data centres The power behind the data Private public businesses, from banks to supermarkets, to telecommunications companies internet providers
Guide to Minimizing Compressor-based Cooling in Data Centers
Guide to Minimizing Compressor-based Cooling in Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By: Lawrence Berkeley National Laboratory Author: William Tschudi
Guideline for Water and Energy Considerations During Federal Data Center Consolidations
Guideline for Water and Energy Considerations During Federal Data Center Consolidations Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
Control of Computer Room Air Handlers Using Wireless Sensors. Energy Efficient Data Center Demonstration Project
Control of Computer Room Air Handlers Using Wireless Sensors Energy Efficient Data Center Demonstration Project About the Energy Efficient Data Center Demonstration Project The project s goal is to identify
Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie
Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie Mukesh Khattar, Energy Director, Oracle National Energy Efficiency Technology Summit, Sep. 26, 2012, Portland, OR Agenda
Reducing Data Center Energy Consumption
Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate
State of the Art Energy Efficient Data Centre Air Conditioning
- White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...
Data Center RD&D at EPRI
Data Center RD&D at EPRI Mukesh Khattar Technical Executive Critical facilities Round Table Meeting Palo Alto, CA 16 October 2015 EPRI Focus for Data Centers RD&D Address problems facing the member electric
Data Center Airflow Management Retrofit
FEDERAL ENERGY MANAGEMENT PROGRAM Data Center Airflow Management Retrofit Technology Case Study Bulletin: September 2010 Figure 1 Figure 2 Figure 1: Data center CFD model of return airflow short circuit
National Grid Your Partner in Energy Solutions
National Grid Your Partner in Energy Solutions National Grid Webinar: Enhancing Reliability, Capacity and Capital Expenditure through Data Center Efficiency April 8, 2014 Presented by: Fran Boucher National
General Recommendations for a Federal Data Center Energy Management Dashboard Display
General Recommendations for a Federal Data Center Energy Management Dashboard Display Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National
White Paper #10. Energy Efficiency in Computer Data Centers
s.doty 06-2015 White Paper #10 Energy Efficiency in Computer Data Centers Computer Data Centers use a lot of electricity in a small space, commonly ten times or more energy per SF compared to a regular
Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC)
Drives and motors A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC) The power behind the data Private and public businesses, from banks to
Drives and motors. A guide to using variable-speed drives and motors in retail environments
Drives and motors A guide to using variable-speed drives and motors in retail environments Improving energy efficiency and lowering the carbon footprint Retailers across the UK take their corporate responsibility
Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
Wireless Sensors Improve Data Center Energy Efficiency
Wireless Sensors Improve Data Center Energy Efficiency Technology Case Study Bulletin: September 2010 As data center energy densities, measured in power per square foot, increase, energy savings for cooling
Analysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
Energy Efficient High-tech Buildings
Energy Efficient High-tech Buildings Can anything be done to improve Data Center and Cleanroom energy efficiency? Bill Tschudi Lawrence Berkeley National Laboratory [email protected] Acknowledgements California
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
3/29/2012 INTRODUCTION HVAC BASICS
INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.
Energy Efficiency. Energy Efficient Home Cooling:
Energy Efficiency Energy Efficient Home Cooling: Choosing an air conditioning system is an important decision. A poor choice may be costly to purchase and operate and yet fail to provide the desired cooling
Creating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
Guidance for Calculation of Efficiency (PUE) in Data Centers
Guidance for Calculation of Efficiency (PUE) in Data Centers White Paper 158 Revision 1 by Victor Avelar > Executive summary Before data center infrastructure efficiency can be benchmarked using PUE or
The Different Types of Air Conditioning Equipment for IT Environments
The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.
Local Dealer: www.cebrands.com
Local Dealer: C.E. LLC - Miami, FL USA www.cebrands.com Res2012-Rev2 QUALITY YOU CAN FEEL Residential Product Line >TCA7,9 Tempstar SmartComfort TXT + Air Conditioner Featuring The Observer Communication
Guidance for Calculation of Efficiency (PUE) in Data Centers
Guidance for Calculation of Efficiency (PUE) in Data Centers White Paper 158 Revision 3 by Victor Avelar Executive summary Before data center infrastructure efficiency can be benchmarked using PUE or other
Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty
Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp
Defining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
Recommendation For Incorporating Data Center Specific Sustainability Best Practices into EO13514 Implementation
Recommendation For Incorporating Data Center Specific Sustainability Best Practices into EO13514 Implementation Version 1.0 - November, 2011 Incorporating Data Center-Specific Sustainability Measures into
Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues
Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
Chilled Water HVAC Systems
Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,
Data Center Metering and Resource Guide. Version 1.1. July 30th, 2015. Rod Mahdavi and Steve Greenberg. Lawrence Berkeley National Laboratory
Data Center Metering and Resource Guide Version 1.1 July 30th, 2015 Rod Mahdavi and Steve Greenberg Lawrence Berkeley National Laboratory Note to users: Please submit comments and suggestions to Steve
I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015
I-STUTE Project - WP2.3 Data Centre Cooling Project Review Meeting 8, Loughborough University, 29 th June 2015 Topics to be considered 1. Progress on project tasks 2. Development of data centre test facility
VertiCool Space Saver 2 to 15 tons Water-Cooled and Chilled Water
2 to 15 tons Water-Cooled and Chilled Water Unique Solutions for Challenging HVAC Projects Your Choice for Limited Space Applications Water-Cooled Chilled Water The VertiCool Space Saver allows installation
7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
A Cover HVAC ENERGY EFFICIENT
A Cover HVAC ENERGY EFFICIENT EQUIPMENT toolkit 1 CONTENTS AND PARTNERS 2 Introduction 3 equipment & processes 3 Optimise operating settings 2 upgrade equipment 4 Seal the building 5 Rearrange air conditioning
Section 2: Estimating Energy Savings and Incentives
Section 2: Estimating Energy Savings and Incentives 2.1 Estimating Energy Savings and Incentives... 2 2.2 Customized Measures - Estimation Software... 2 2.2.1 AC&R I - High Efficiency Chiller... 3 2.2.2
Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres
What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy
CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
Data Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics
On January 13, 2010, 7x24 Exchange Chairman Robert Cassiliano and Vice President David Schirmacher met in Washington, DC with representatives from the EPA, the DOE and 7 leading industry organizations
Recommendations for Measuring and Reporting Overall Data Center Efficiency
Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 2 Measuring PUE for Data Centers 17 May 2011 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations for Measuring
HVAC Efficiency Definitions
HVAC Efficiency Definitions Term page EER - 2 SEER - 3 COP - 4 HSPF - 5 IPLV - 6 John Mix May 2006 Carrier Corporation 1 Energy Efficiency Ratio (EER) The energy efficiency ratio is used to evaluate the
Data Center Energy Use, Metrics and Rating Systems
Data Center Energy Use, Metrics and Rating Systems Steve Greenberg Energy Management Engineer Environmental Energy Technologies Division Lawrence Berkeley National Laboratory October 31, 2007 Today s s
Commissioning - Construction Documents (Page 1 of 6)
Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem
Minimising Data Centre Total Cost of Ownership Through Energy Efficiency Analysis
Minimising Data Centre Total Cost of Ownership Through Energy Efficiency Analysis Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. [email protected]
Alan Matzka, P.E., Senior Mechanical Engineer Bradford Consulting Engineers
Information Technology and Data Centers HVAC Showcase November 26, 2013 Alan Matzka, P.E., Senior Mechanical Engineer Bradford Consulting Engineers Welcome. Today s webinar is being recorded and will be
European Code of Conduct for Data Centre. Presentation of the Awards 2014
European Code of Conduct for Data Centre Presentation of the Awards 2014 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results European
Lesson 36 Selection Of Air Conditioning Systems
Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section
Recommendations for Measuring and Reporting Overall Data Center Efficiency
Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 1 Measuring PUE at Dedicated Data Centers 15 July 2010 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling
COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers
COMMERCIAL HVAC CHILLER EQUIPMENT Air-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They
HVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
The Data Center Dilemma - A Case Study
Second Place: Industrial Facilities or Processes, Existing The TCS data center makes use of white cabinets and reflective surfaces as one method to reduce power for its lights and cooling. Data Center
DC Pro Assessment Tools. November 14, 2010
DC Pro Assessment Tools November 14, 2010 William Tschudi, PE Lawrence Berkeley National Laboratory [email protected] 510-495-2417 1 Slide 1 Assessment tools LBNL is developing tools to assist in performing
Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany
Life Cycle Costing Analysis of Water-cooled Chillers Chillventa Nuremburg, Germany Spring 2012 Description Life Cycle Cost Analysis is a method of determining and comparing the total costs of investment
Heating, Ventilation & Air Conditioning Equipment
FinAnswer Express Utah Incentive Catalog Effective as of May 19, 2012 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy-efficient technologies.
How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems
How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems Paul Mathew, Ph.D., Staff Scientist Steve Greenberg, P.E., Energy Management Engineer
Failure code manual. content
Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一
KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005
KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO SAUDI STANDARD DRAFT No. 3457/2005 NON-DUCTED AIR CONDITIONERS AND HEAT PUMPS TESTING AND RATING PERFORMANCE This standard is developed
Data Center. Ultra-Efficient chilled water system optimization. White paper. File No: 9.236 Date: december 03, 2015 Supersedes: new Date: new
Data Center Ultra-Efficient chilled water system optimization White paper File No: 9.236 Date: december 03, 2015 Supersedes: new Date: new Data Center - Ultra-Efficient white paper 3 abstract The primary
In Row Cooling Options for High Density IT Applications
In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions
How To Design A Building In New Delhi
ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption
It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.
The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as
Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
Self-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10. Sponsored by:
Self-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10 Sponsored by: Disclaimer This document was prepared as an account of work sponsored by the United States Government.
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce
Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures
Data Realty Colocation Data Center Ignition Park, South Bend, IN Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Project Overview Data Realty is a data center service provider for middle
Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes
Precision Cooling for Business-Critical Continuity Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes We re Emerson Network Power, backed by Emerson,
HVAC Applications. VFD considerations for HVAC systems...
HVAC Applications VFD considerations for HVAC systems... 1 COMMON TERMINOLOGY VFD (VARIABLE FREQUENCY DRIVES) AFC (ADJUSTABLE FREQ. CONTOLLER) ASD (ADJUSTABLE SPEED DRIVES) VSD (VARIABLE SPEED DRIVES)
Managing Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
MAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
STULZ Water-Side Economizer Solutions
STULZ Water-Side Economizer Solutions with STULZ Dynamic Economizer Cooling Optimized Cap-Ex and Minimized Op-Ex STULZ Data Center Design Guide Authors: Jason Derrick PE, David Joy Date: June 11, 2014
- White Paper - Data Centre Cooling. Best Practice
- White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH
Calculating Total Cooling Requirements for Data Centers
Calculating Total Cooling Requirements for Data Centers By Neil Rasmussen White Paper #25 Revision 2 Executive Summary This document describes how to estimate heat output from Information Technology equipment
AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries
AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries Hot tips and cool ideas to save energy and money! Air conditioning units or systems are often used by foundries
HVAC Preventative Maintenance Basics. Presented by Mike Crawley
HVAC Preventative Maintenance Basics Presented by Mike Crawley Air Handlers/Package Units: Coils have to be clean! The main purpose of any coil is to absorb or reject heat If coils are dirty; air flow
Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc.
Business Management Magazine Winter 2008 Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Contrary to some beliefs, air is quite
Midea Commercial Air Conditioner Malfunction Handbook
Midea Commercial Air Conditioner Malfunction Handbook May 1, 2008 Customer Service Philosophy of Midea Air Conditioner Service Target: 100% Customer Satisfaction Service Standard: 100% Earnestness Service
New Deluxe Wall Mounted Heat Pump Series EXTERIOS
New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
Technical Systems. Helen Bedford
Technical Systems in Data Centres Helen Bedford Technical Systems in Data Centres Overview Cooling IT and Peripheral Equipment Security: Access and Control Building Management System (BMS) Data Centre
