ACS-30-EU-EMDR-10-MOD
|
|
|
- Mitchell Hill
- 10 years ago
- Views:
Transcription
1 Multi-application heat tracing Control and Monitoring in commercial and residential buildings Roof & Gutter de-icing sensor module Technical Information Approvals Module IP rating Ambient operating temperature range Mounting Enclosure Dimensions Enclosure type Connections Description The Raychem ACS-30-EU-EMDR-10-MOD Module for the ACS-30 system provides smart sensor input for roof & gutter de-icing applications. The module provides temperature & moisture sensing input. The module can be positioned near to the heated area and is connected to the PCM module via a 3-wire cable. The module is provided with a 4m external temperature and moisture sensor to be positioned at the heated surface. The sensor cold lead cable can be extended to a maximum length of 100 m (using 3 x 1.5 mm2 cable.) The output from the ACS-30-EU-EMDR-10-MOD module enables the switching of the heating circuits within the power & control module (PCM). CE Marked. IP55 (enclosure with control device) 0 to +35 C (enclosure with control device) Wall mounting 332 mm x 262 mm x 132 mm Polystyrene box and polypropylene cover 4 Polyamide Cable Glands (IP68 rated) with stopping plugs Control Device Device name EMDR-10 Supply voltage 230 Vac, +/ 10%, 50Hz Power Consumption 4VA max. Measuring accuracy +/ 1.5K Operating differential +/ 0.5K Moisture Sensor (output) I max 1A/230 VAC, SPST potential 230 VAC with fuse 5 X 20 mm T315 ma according to IEC127-2/V Terminals 2.5 mm2 (stranded conductors), 4 mm2 (solid conductors) Ambient Sensor (VIA-DU-A10) PTC Sensor (IP54). Cable not included. Max length 100 m (2 x 1.5 mm2). Ambient operating temperature range 30 C to +80 C Terminals 2.5 mm2 Mounting Wall mounting Moisture Sensor (HARD-45) PTC Sensor. Supplied with 4 m cold lead. Extendable to 100 m (3 x 1.5 mm2). Power consumption 9 W to 18 W Ambient operating temperature range 30 C to +65 C continuous Supply voltage 230 VAC, +/ 10%, 50Hz (via control device) 1 / 8
2 1. Installation and Safety Remarks Select a suitable location for the enclosure and mount it on a wall using suitable screws. Install power cable, moisture and ambient sensor cables, RTD cables (which have to be connected in the ACS-30-EU-PCM2 module) into the enclosure using the glands supplied. Keep stopping plugs in unused gland entries. Remarks: Only for electricians! Attention: mistakes during connection of the device can cause damage to the control unit. Pentair Thermal Management is not liable for any damage caused by faulty connections and/or incorrect handling. Before working on the device, switch off the power supply! The device may only be connected and serviced by authorised, trained electricians. Electrical connection must be carried out in accordance with the enclosed connection diagram. The wires of the moisture sensor carry mains voltage, those of the temperature sensor and the alarm contact have to be considered as carrying mains voltage in consideration of VDE and the relevant installation regulations must be observed. Do not lay sensor cables together with other live wires in order to avoid electromagnetic interference. Local standards for electrical connection must be observed. If the device does not operate as expected, please check all connections and the mains power supply. 2. Installation and Dimensions of the Temperature Sensor A good positioning of the temperature sensor is crucial for the correct and efficient operation of the snow melting system. The temperature sensor should be placed on the North side of the building, in a position where it will always be away from direct sunlight. Moreover, it must be protected against other influencing factors such as being mounted above doors or windows or close to lamps or floodlights. A position on the wall just below a gutter is recommended. The connection wire of the sensor may be extended to max. 100 m at a lead diameter of 1.5 mm2. The wires of the temperature sensor has to be considered as carrying mains voltage according to VDE. The relevant installation regulations must be observed. Connection diagram see paragraph 6. Dimensions: / 8 EN-RaychemACS30EMDR10-DS-EU0011 Rev2 THERMAL building SOLUTIONS
3 3. Installation and Dimensions of the Moisture Sensor A good positioning of the moisture sensor is crucial for the correct and efficient operation of the snow melting system. The moisture sensor and heating cable(s) served / controlled by the same control unit should be positioned in the same roof area. The moisture sensor is usually placed in a gutter at the lowest position in the system adjacent to one of the drainpipes. This is usually where water / snow is last cleared from the gutter, hence ensuring that the whole protected area is cleared before the heating system turns off. The exact positioning will depend on the particular building and the prevailing weather conditions. If the system shuts down before snow is removed from a key area, then the sensor should be moved to that area. For mounting the sensor in the gutter use the fixing brackets (Hard-46) to fix the sensor adjacent and parallel to the heating cable. Ensure that the sensor remains flat and is not in contact with the heating cable. The connection wire of the moisture sensor may be extended to max. 100 m at a lead diameter of 3 x 1.5 mm2. Connection diagram see paragraph 6. The wires of the moisture sensor are carrying mains voltage! 4 m 650 Dimensions: active sensor length x 6 Ø 9, 5 4. Function R EMDR-10 AC 230V 50/60Hz IP C Relais: 10(4)A, AC 230V Alarm: 2(1)A, AC 230V Do not open while energized Nicht unter Spannung öffnen Ne pas ouvrir sous tension TEST C min T315mA IEC127 2/V PE PE PE The control unit has four LEDs for indication of the operating conditions and four dials for the adjustment of different parameters. The air temperature is measured by means of a temperature sensor. When the air temperature falls below the value adjusted at the control unit, then the corresponding yellow LED will light up and after approx. 10 minutes the moisture sensor is activated. If moisture is present at the sensor then the corresponding yellow LED will light the controller will provide the signal to the PCM to switch ON the heater, as will the red LED. The heating cable remains on until the air temperature rises above the set value the moisture falls below the set value the air temperature falls below the adjusted lower temperature limit and the set post-heating period has elapsed. 4.1 Display Elements The LEDs indicate following operating conditions: LED green Device in operation (mains voltage) LED yellow Adjusted air temperature threshold exceeded LED flashes in case of fault at the air temperature sensor (break or short circuit) LED yellow Adjusted moisture threshold exceeded LED flashes in case of fault at the moisture sensor (break) LED red Status of heater ON 3 / 8
4 4.2 Parameter Adjustments The following parameters can be set by means of the respective dial: Adjustment of the air temperature threshold. The moisture sensor is being put into operation below this value Adjustment of the moisture threshold. Above this value the heating cable is being energized, if the air temperature is below the setpoint. 1 = max. sensitivity, 10 = min. sensitivity Adjustment of the lower temperature limit. Below this value the heating cable will be switched off. At the same time the moisture measurement will be switched off. In addition this dial can be used to test the unit by turning the potentiometer shaft fully to the left. After that the heating cable will be energized for max. 10 minutes. If the shaft is turned to the right again during these 10 minutes then the TEST will be stopped and the unit works in normal operation mode with the adjusted lower temperature limit. If the potentiometer is left in the TEST position then the unit will automatically return to normal operation mode after the test period of 10 minutes and works with a lower temperature limit of 25 C This lower temperature limit can be set to a different value at any time. A new test period can be activated by turning the shaft from fully left position to the right and then back again to the left stop min Adjustment of the post-heating period. The correct adjustment of the post-heating period is dependent on the local weather conditions, the location, and the requested heating power. The conditions have to match the requirements for an economical operation. Minimum time over which the heating cable stays activated when the conditions of temperature and humidity are no longer met e.g. temperature increases above set level or moisture is lower than set level. Use the following table as a guide: Description Suggested setting Air temperature threshold +2 C Moisture threshold 5 Lower temperature limit 15 C Post-heating period 60 minutes Periodic inspection: It is recommended to inspect and test the control unit as well as the heating cable circuits annually. 4.3 Moisture Sensor Fuse The control unit is equipped with a fuse in the output for the moisture sensor which protects this output against overload and short circuit. In case this fuse requires replacement you may exclusively use a fuse (5 x 20 mm) type T315mA according to IEC127-2/V. Other fuse types are not permissible and may lead to damage of the unit. 4 / 8 EN-RaychemACS30EMDR10-DS-EU0011 Rev2 THERMAL building SOLUTIONS
5 5. Fault Messages and Trouble Shooting The following faults are being detected by the control unit: Fault Break or short circuit of the temperature sensor Break of the moisture sensor Short circuit of the moisture sensor Power failure Reaction LED temperature flashes, alarm relay and load relay switch off LED humidity flashes, alarm relay and load relay switch off Additionally, under short circuit conditions, Moisture sensor fuse will rupture. Alarm relay and load relay switch off Notice: A short circuit at the moisture sensor leads to the triggering of the fuse. In case of a fault at the moisture sensor the moisture measuring circuit will be switched off. The LED moisture will continue to flash. After repair of the moisture sensor the fault signal has to be cleared by activating the TEST mode (turn the potentiometer for the lower temperature limit to the left stop and shortly after that back again to the requested lower temperature limit). When the air temperature falls below the value adjusted at the control unit, then the moisture sensor is activated and tested again after approx. 10 minutes. Trouble shooting: Symptoms Probable causes Correction Status of heater OFF active (snow is not melting) Temperature below set point, but status of heater OFF active Snow present, but status of heater OFF active Snow begins to clear, but the status of the heater turns off too soon Moisture sensor not positioned correctly (e.g. not flat in the gutter) Sensor section of this manual Temperature sensor located in direct sunlight Moisture not detected Less than 10 minutes have elapsed since the temperature fell below the setpoint below the setpoint Moisture dial set too high Poor positioning of the moisture sensor Poor positioning of the moisture Moisture dial set too low Temperature has fallen below minimum temperature setpoint Re-position following the instructions in the Assembly of the Moisture Re-position following the instructions in the Assembly of the Temperature Sensor section of this manual This is normal operation: low temperature AND moisture must be detected before the heating cable is energized The moisture sensor is not checked for the presence of moisture until 10 minutes after the temperature falls Set the moisture dial to a lower value Re-position following the instructions in the Assembly of the Moisture Sensor section of this manual Re-position following the instructions in the Assembly of the Moisture Sensor section of this manual Set the moisture dial to a higher value This is normal operation 5 / 8
6 6. Wiring Diagram 6.1 EMDR-10 with directly connected Heating Cable Attention: max. heating cable length 40 m, circuit breaker max. 10A (C-characteristic) L N PE ACS-30-EU-EMDR-10-MOD U1 EMDR-10 DC AC load Moisture sensor COM NC NO Alarm PE PE PE N N N L L LS T1 T2 ALARM 1.5 mm 2 Y ellow/green 1.5 mm 2 BLUE CLAIR 1.5 mm 2 BLACK A1 K1 A2 1mm 2 ORANGE X 1mm 2 ORANGE 1mm 2 ORANGE 11 1mm 2 ORANGE PL PL PL X 51,1 Ω 200 Ω Moisture Sensor Ambient Sensor To RTD input on ACS-30-EU-PCM2 Output from the ACS-30-EU-EMDR-10-MOD is equivalent to an RTD connected as shown below: / 8 EN-RaychemACS30EMDR10-DS-EU0011 Rev2 THERMAL building SOLUTIONS
7 Part Numbering and Ordering Description PCN Product Name Description EAN Code ACS-30-EU-EMDR-10-MOD Roof & Gutter de-icing sensor for ACS Related Products PCN Product Name Description EAN Code ACS-30-EU-UIT2 User Interface module for the ACS-30 Control and Monitoring System ACS-30-EU-VIA-DU-20-MOD Snow melting and surface de-icing sensor module for the ACS-30 Control and Monitoring System ACS-30-EU- Remote monitoring module for the ACS Moni-RMM2-E Control and Monitoring System ACS-30-EU-PCM2-5-20A Power Control Module for ACS (5 circuit module with 20 Amp ACS-30-EU-PCM A Power Control Module for ACS (10 circuit module with 20 Amp ACS-30-EU-PCM A Power Control Module for ACS (15 circuit module with 20 Amp ACS-30-EU-PCM2-5-32A Power Control Module for ACS (5 circuit module with 32 Amp ACS-30-EU-PCM A Power Control Module for ACS (10 circuit module with 32 Amp ACS-30-EU-PCM A Power Control Module for ACS-30 (15 circuit module with 32 Amp / 8
8 United Kingdom Tel: Fax: Ireland Tel: Fax: All Pentair trademarks and logos are owned by Pentair or its global affiliates. Pentair reserves the right to change specifications without prior notice Pentair. 8 / 8
Power Supply and Indicator Unit Type 5024-1. Fig. 1 Type 5024-1. Mounting and Operating Instructions EB 9539 EN
Power Supply and Indicator Unit Type 5024-1 Fig. 1 Type 5024-1 Mounting and Operating Instructions EB 9539 EN Edition October 2003 Application 1 Application The Type 5024-1 Power Supply and Indicator Unit
DALI RC BASIC SO. Control unit Operating instructions
DALI RC BASIC SO Control unit Operating instructions Contents Safety... 4 General instructions 4 Safety instructions 4 Description... 5 Purpose and application 5 Function 5 Light control 5 Brightness
RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC
Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage
BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell
Data, installation, operation and maintenance 4 & 8 Zone Fire Panels Zircon range BARDIC by Honeywell LED flashing LED Continuous FAULT DISABLE/TEST Power General Fault Sounder Fault/ Disable System Fault
Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.
Product and Applications Description The power supply units N 125/x2 can supply DC 24 V power from an additional pair of terminals (yellowwhite). This DC 24 V output voltage can be used to power e.g. an
CO2 Alarm. Operation. Application
CO Alarm 100-77V AC Supply Voltage Two pre-configured alarm and control thresholds Thresholds factory set to customer requirements on dispersive infrared sensing technology Optional internal audible alarm
Speed Control Relays SX2
SX2 File 850 CONENS Description.....................................................Page General Information................................................ 2-3 SX2DV General Information...........................................
Product overview. 2000 mm. 100 mm
Panel mounted electronic multi-circuit heat-tracing control, monitoring and power distribution system Product overview CABLE DUCT Card Rack Modules TERMINAL STRIP PLINTH MAIN SWITCH 800 mm USER INTERFACE
HERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
Fire Alarm Control Panel. Family. Operating Manual
Fire Alarm Control Panel Family Operating Manual CONTENTS System Description AH-03312 System Characteristics... Fire Signal Receiving Board Description-4L... Fire Signal Receiving Board Description-8L...
Color Mark Sensor with Red or Green LED E3S-VS
Color Mark Sensor with Red or Green LED Rugged IP67 Color Mark Sensor 1 ms response time Detects a wide variety of color marks PNP or NPN output ls Light-on/ Dark-on operation, wire selectable Vertical
Electronic Pressure Switch EDS 300
Electronic Pressure Switch EDS 300 User manual Page 2 of 16 Content 1. Functions of the EDS 300...3 2. Mounting...3 3. Operating keys on the membrane keypad...4 4. Digital display...4 5. Output function...5
Operating Instructions. Room temperature controller
Operating Instructions 1. Area of application The room temperature controller is used to regulate the temperature in closed rooms such as flats, schools, function suites, workshops, etc. Safety instructions
INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930
INSTALLATION GUIDE Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 Card Reader and Controller Model 3.5 with KIM Swipe Reader Table of Contents 1. Features..................................
PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624
PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624 v.1.0 AC/AC power supply unit Edition: 1 from 24 th October 2008 Supercedes edition: ---------- 10062009 CONTENTS: 1. Technical description. 1.1. General description
Product and functional description
Product and functional description The KNX / DALI gateway N 141/02 is a 4 MU wide, DINrail mounted KNX device with one DALI interface to which up to 64 DALI actuators (e.g. DALI ballasts) can be connected
WD-AMX Water Detection Controllers
Page 1 of 5 WD-AMX Water Detection Controllers Features: Benefit: LED Status of leak status VFC output Audible alarm Auto or manual reset alarm output Uses an isolated AC signal which prevents oxidation
Water Leak Detection System
Water Leak Detection System Installation and Operating Manual 505-334-5865 ph 505-334-5867 fax www.rodisystems.com email:[email protected] 936 Highway 516 Aztec, NM 87410-2828 Manual Revisions and Copyright
CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.
425 CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE General purpose single phase thyristors and solid state relays Product data abc 425 EUROCUBE A complete range of low cost solid state relays and
Heating, air-conditioning, cooling
Series description Design High efficiency, single stage, low pressure, inline centrifugal pump Supplied with EC motor and electronic duty adaptation Available in glanded construction, mechanical shaft
FIRERAY 2000 Installation Guide
FIRERAY 2000 Installation Guide Features Range 33ft to 330 ft. 24Vdc operation Selectable alarm thresholds Low current consumption Ground level electronics Manual or Automatic reset System Description
Three-phase monitoring relay CM-PFE
Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics
HM-W536 Install Guide
HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.
RMM2 Heat-Tracing Remote Monitoring Module for the Raychem NGC Control System Installation Instructions
Heat-Tracing Remote Monitoring Module for the NGC Control System Installation Instructions Tools Required 3 mm slotted screwdriver 3/8 hex key (for -4X only) Approvals Nonhazardous locations Type NM LISTED
DEK-REL- 24/1/SEN. Extract from the online catalog. Order No.: 2964050
Extract from the online catalog DEK-REL- 24/1/SEN Order No.: 2964050 Relay terminal block for sensor, with soldered-in miniature relays, contact (AgNi+Au): small to medium loads, 1 N/O contact, input voltage
NGC-30-CR -CRM -CRMS -CTM -CVM
NG-0-R -RM -RMS -TM -VM ontrol and monitoring modules for use with the Raychem NG-0 Installation Instructions Description The NG-0-RM/-RMS and NG-0-TM provide ground-fault and line current sensing, alarming,
RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters
Characteristics multifunction voltage control relay RM35-U - range 15..600 V Complementary Reset time Maximum switching voltage [Us] rated supply voltage Supply voltage limits Power consumption in W Main
RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems
3 072 RDJ10RF RCR10/433 Wireless room temperature controller with 24-hour time switch and LCD Programmable, for heating systems RDJ10RF/SET Operating modes: Automatic, Comfort, Energy Saving, and Frost
Shunt lock function 3066
Version: January 2004 Contents Alarm System Activation unit Deactivation unit Digital locking cylinder or Smart Relay 1.0 Method of Operation 4 1.1 General 4 1.2 Turning the Alarm System On 4 1.3 Turning
Shutter Actuator Standard, 4-fold, 230 VAC, MDRC RA/S 4.230.1, GH Q631 0076 R0111. ABB i-bus EIB
, GH Q631 0076 R0111 2CDC 071 240 F0003 The Shutter Actuator Standard is used to control a maximum of four independent 230 VAC drives for positioning shutters, blinds, awnings and other hangings as well
Safety technique. Emergency stop module BO 5988 safemaster
Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1
Freeze Protection Thermostats MODELS SST 2. Installation and Operation Manual
Freeze Protection Thermostats MODELS SST 2 Part Number 22744 MANUAL We Manage Heat Installation and Operation Manual Environmental Technology, Inc. 1850 N Sheridan Street South Bend, Indiana 46628 (574)
For UK only RXL39.1 and the applications package SP-03 are sold in the United Kingdom only.
s For UK only RX39.1 and the applications package SP-03 are sold in the United Kingdom only. 3 876 3876P01 RX Room controller Communicating controllers for fan-coil applications SP-03 RX39.1 The RX39.1
Digital input modules
8 172 TX-I/O Digital input modules TXM1.8D TXM1.16D Two fully compatible versions: TXM1.8D: 8 inputs, each with a three-color LED (green, yellow or red) TXM1.16D: As TXM1.8X, but 16 inputs, each with a
Drayton Digistat +2RF/+3RF
/+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer
How To Use A Power Supply Unit (Upu)
BRAVER UPS (Uninterruptible Power System) User s Manual Safety CAUTION! This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user replaceable parts.
Technical data. General specifications. Indicators/operating means. 30 Hz Multiplex operation 30 Hz / n, n = number of sensors, n 5
Model Number Single head system Features Parameterization interface for the application-specific adjustment of the sensor setting via the service program ULTRA 000 programmable switch outputs Hysteresis
DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
Introduction. Refrigerant Leak Detecting System. Feature and Benefits
PSC European Refrigeration Controls Catalogue Catalog Section 9 Product Bulletin PD-GAS-E Refrigerant Leak Detecting System Introduction This range of refrigerant leak detecting systems is designed for
Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
W150: Miniature photoelectric switch series with completely integrated electronics
Product group W50 Photoelectric proximity switch BGS Photoelectric proximity switch energ. Photoelectric reflex switch W50: iniature photoelectric switch series with completely integrated electronics Through-beam
1 Safety instructions. 2 Device components. 3 Function. Leader in Led solutions. Compact presence detector. Operating instructions
Compact presence detector Operating instructions 1 Safety instructions Electrical equipment may only be installed and fitted by electrically skilled persons. Failure to observe the instructions may cause
Floodlight Range Installation Guide
SPARTAN Floodlight Range Installation Guide CML13ATEX3007 IEC Ex CML14.0001 This installation guide provides instructions for installing the Infra-Red and White-Light SPARTAN SPX series of explosion protected
HSP GmbH Zum Handwerkerhof 2 90530 Wendelstein Tel. 09129 / 2852-0 Fax: 09129 / 2852-11 Web: www.hsshsp.de EMAIL: [email protected] NTG-3000.
NTG-3000 Transducer Data Sheet Document Version 2.8 Page 1 of 10 Versions / Revisions: Document Creation Author Description version date 2.0 2012-07-25 P. Compensis First official version 2.1 2012-08-24
AUTODIALLER / QUICKDIALLER - SA132
AUTODIALLER / QUICKDIALLER - SA132 INSTRUCTION LEAFLET ENGLISH www.thermomax-group.com CONTENTS 1 SETUP AT A GLANCE... 2 2 FOREWORD....... 3 3 INSTALLATION...... 4 4 KEYPAD AND INDICATORS...... 5 SETTING
Problem / Solution. The problem:
Problem / Solution Solar Photovoltaic (PV) technology has shown significant development in recent years and this has led to many UK homeowners investing in Solar PV installations. Solar electricity is
Current Monitoring Kit QUICK START GUIDE
Current Monitoring Kit QUICK START GUIDE Pico Technology EL040 Current Monitoring Kit Quick Start Guide CONTENTS 1 Introduction... 1 2 Kit contents... 3 3 Installation... 3 3.1 Connecting the system together...
Infrarot-Bewegungsmelder IP44
Infrarot-Bewegungsmelder IP44 infrared motion sensors IP44 ODA (weiß) slim ODA (schwarz) slim 95174 96000 ODA (weiß) ODA (schwarz) 95175 96001 Betriebsanleitung User s Manual User s Manual infrared motion
Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact
Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only
Pressure monitoring equipment for oil-sf 6. bushings, type GOEK
Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and
Current Monitoring Kit
Current Monitoring Kit QUICK START GUIDE DO090-6 CONTENTS Issues: 1) 2.10.02 WP A4 format 2) 2.10.02 Added safety warning 3) 17.3.06 Word A5 format. S1: Removed relay modules. S2: Added MI010. S4.1: added
Operating instructions IV / 2007
General Operating instructions IV / 2007 Contents General Installation Application and function Application and function... 2 Safety information... 2 Design and dimensions... 3 Wiring diagram... 3 Installation
How To Read A Pipe From A Sensor
Liquid Level Sensor Installation on pipes. Sensing by means electrostatic capacity and is not influenced by the color of the pipe or liquid. Available in 8 to mm dia. and to mm dia. models to enable sensing
COLOR VIDEO DOOR PHONE CDV-71BE/D
COLOR VIDEO DOOR PHONE CDV-71BE/D 513-11, Sangdaewon-dong, Jungwon-gu, Seongnam-si, Gyeonggi-do, Korea Int l Business Dept. : Tel.; +82-31-7393-540~550 Fax.; +82-31-745-2133 Web site : www.commax.com Printed
Meter Relays. 077 Series Analogue Meter Relays. Features. Applications
077 Series Analogue Features Monitors and controls any variable which can be converted to an A.C. or D.C. signal. Rugged, shock and vibration resistant design Indicator, relays and power unit in one housing
Electronic Control Devices The European Product Catalogue 2007
FX07 Field Controller (1/4) FX07 Field Controller Display Model Dimensions in mm (inches) The FX07 is a terminal unit controller in the Facility Explorer range of products. The controller is designed specifically
Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet
Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order
SECURITY SYSTEM ADP-CAN
INSTALLATION INSTRUCTION SECURITY SYSTEM ADP-CAN Introduction Motorcar security system ADP-CAN is for motorcars provided with CAN net. It is for the work with the motorcar factory security systems or remote
PSDC 08128. PSDC 12V/8A/8x1A Power supply for up to 8 analog cameras PTC/TOPIC.
PSDC 08128 v.1.2 PSDC 12V/8A/8x1A Power supply for up to 8 analog cameras PTC/TOPIC. EN** Edition: 9 from 25.05.2015 Supersedes the edition: 8 from 12.12.2014 the 8x 1A/12V DC power output for powering
Danfoss Link Mobile Phone Butler
MAKIG MODER LIVIG POSSIBLE Installation Guide www.heating.danfoss.com Table of Contents 1 Introduction... 3 2 Installation... 3 3 Interfaces... 4 4 Wiring... 4 5 SMS Commands... 5 6 Technical Specifications...
Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency
echnical data sheet NV24A--RE Communicative globe valve actuator for 2-way and 3-way globe valves Actuating force 1000 N Nominal voltage AC/DC 24 V Control Modulating DC (0)2...10 V Variable Nominal stroke
T5000 T000 LCD Digital Fan Coil Thermostat
T5000 T000 LCD Digital Fan Coil Thermostat T000 LCD Digital Fan Coil Thermostat T000 LCD Digital Fan Coil Thermostats are designed to control heating, cooling, or year round air conditioning unit in Commercial,
RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER
Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.
GSM AUTO DIALER. Remote Monitoring & Control using your mobile phone. www.gsm-activate.co.uk
GSM AUTO DIALER Remote Monitoring & Control using your mobile phone www.gsm-activate.co.uk Product Information Our GSM Auto-Dialer is a versatile unit which can be attached to many of your electronic devices
ABLOY DA60 SWING DOOR OPERATOR Installation and commissioning manual Abloy Oy An ASSA ABLOY Group company APPROVALS / STANDARDS Low Voltage directive 7//EEC as amended by the directive 9/68/EEC EMC directive
7 Lighting Technology
7 Lighting Technology Series HS6145 For use in Zone 1 and Zone 2 Comply with requirements of Fire Department standard DIN 14 462 Battery state display Deep discharge protection Open circuit monitor Light
Laser diffuse reflection light scanner with background suppression. Dimensioned drawing
Specifications and description HRTL 3B Laser diffuse reflection light scanner with background suppression Dimensioned drawing We reserve the right to make changes DS_HRTL3B_en.fm en 01-2010/12 50114049
REGULINE 600VA / 1000VA REGULATOR USER MANUAL
REGULINE 600VA / 1000VA REGULATOR USER MANUAL TUNÇMATİK REGULINE SERIES AUTOMATIC VOLTAGE REGULATOR Models: REGULINE 600VA / REGULINE 1000VA Principle of Operation Automatic Voltage Regulators regulate
920 Series. Dual-point heat-tracing control system. Product overview. 920*E4FWL*SIS302*SS3102 shown
Self-Regulating 920 Series Dual-point heat-tracing control system Power-Limiting Mineral Insulated 920*E4FWL*SIS302*SS3102 shown Product overview The DigiTrace 920 is a compact, full-featured, microprocessor-based,
Manual for Fire Suppression & Methane Detection System
Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327
Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications.
Safety Technique SAFEMASTER Emergency Stop Module BG 5924, IP 5924 Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592 BG 5924 IP 5924 Product Description
EPSOLAR LS0512R / LS0524R. Solar Light Controller INSTRUCTION MANUAL. Please read this manual carefully before using the product!
EPSOLAR LS0512R / LS0524R Solar Light Controller INSTRUCTION MANUAL Please read this manual carefully before using the product! LandStar LS0512R / LS0524R Solar Light Controller Nominal system voltage
VIBRATION MONITORING OF FANS INSTALLED IN ROAD TUNNELS
VIBRATION MONITORING OF FANS INSTALLED IN ROAD TUNNELS CEMB SPA Via Risorgimento, 9 Mandello del Lario (Lc), Italy [email protected] www.cemb.com INSTRUMENT FOR MONITORING VIBRATIONS OF FANS INSTALLED IN ROAD
basicdim DGC Compact control module
luxctrol lighting control sstem DGC Compact control module Product description Compact dimensions for luminaire installation For up to 0 DSI or LI ballasts ( per output channel) LI IN input LI/DSI output
48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0.
48 Series - Relay interface modules 8 A Features 48.12 2 Pole Safety relay interface modules, 15.8 mm wide 48.12-2 Pole 8 A (screw terminal) DC sensitive coils Relay with forcibly guided contacts according
Digital Pressure Measuring Instrument MDR480
Description The digital panel instrument MDR480 is designed to measure, display, and monitor pressures in industrial applications. The instrument is panel mounted with a front frame dimension of 96 mm
WATER LEAK DETECTION SYSTEM WLDS-10 INSTALLATION & COMMISSIONING
WATER LEAK DETECTION SYSTEM WLDS-10 INSTALLATION & COMMISSIONING DESCRIPTION: An electronic control panel used in conjunction with one pulse meter (water meter with pulse output proportional to flow rate)
ABB i-bus EIB / KNX Analogue Input AE/S 4.2
Product Manual ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Intelligent Installation Systems This manual describes the functionality of Analogue Input AE/S 4.2. Subject to changes and errors excepted. Exclusion
Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information
Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC
Heating Controller. Building Technologies HVAC Products
2 474 Heating Controller RVP300 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones with or
DRM75A 230V 20/100A DIN rail single phase two wire energy meter
DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation
Cross-beam scanning system to detect slim objects. 100 mm 3.937 in
891 Object Area Sensor General terms and conditions... F-17 Related Information Glossary of terms... P.1359~ Sensor selection guide...p.831~ General precautions... P.1405 PHOTO PHOTO Conforming to EMC
victron energie USER MANUAL GEBRUIKSAANWIJZING GEBRAUCHSANWEISUNG Victron Atlas 12/850
victron energie USER MANUAL GEBRUIKSAANWIJZING GEBRAUCHSANWEISUNG Victron Atlas 12/850 SECTIONS ENGLISH 1 NEDERLANDS 27 DEUTSCH 55 This page intentionally left blank. ENGLISH USER MANUAL Victron Atlas
HCE80/HCC80/HCE80R/HCC80R
HCE80/HCC80/HCE80R/HCC80R UNDERFLOOR HEATING-ZONEING CONTROLLERS PRODUCT DATA FEATURES Easy and fast installation because the new wiring design Pluggable terminals for fast wiring connection because clamp
MOUNTING AND OPERATING INSTRUCTIONS
MOUNTING AND OPERATING INSTRUCTIONS CF 51/55 1. Delivery CF 51/55-1 calculator with battery (optionally with mains power supply) - 1 wall mounting bracket - package with material for sealing, screws, wall
MICROSENS. Central 48 V DC Power Supplies for PoE-Components. Description. Features
Central 48 V DC Power Supplies for PoE-Components MICROSENS Description Active network equipment which is supporting the Power-over-Ethernet functions, typically requires a powerful 48 V DC power supply.
Advantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
RI-215A Operator s Manual. Part Number: 71-0045RK Revision 0 Released: 10/3/05
RI-215A Operator s Manual Part Number: 71-0045RK Revision 0 Released: 10/3/05 Warranty RKI Instruments, Inc., warrants gas alarm equipment sold by us to be free from defects in materials and workmanship,
GAE953 Electrical Alarm Unit 19" with Indicator
Master Instruction 08.95 MI EIO2211 A-(en) GAE953 Electrical Alarm Unit 19" with Indicator The electrical alarm unit GAE953 gives a signal when one or two set alarm values have been exceeded. Input signals
RM4TG20 three-phase network control relay RM4-T - range 200..500 V
Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking
Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages The CM-ESS.M is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.
1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay
Air damper actuators
4 634 OpenAir TM Air damper actuators GDB...1 GLB...1 Rotary version, / AC 230 V Electronic motor driven actuators for three-position and modulating control Nominal torque 5 Nm (GDB), 10 Nm (GLB) Mechanically
Technical Overview Add-on Sensors - Smoke Alarm. Get yours direct at: 01491 410913 www.theclimate.co.uk
Technical Overview Add-on Sensors - Smoke Alarm Get yours direct at: 01491 410913 www.theclimate.co.uk OVERVIEW This kit contains a standard smoke alarm and relay pattress. The Kidde Smoke Alarm supplied
RVL470. Heating Controller. Building Technologies HVAC Products. Series B
2 522 Heating Controller Series B RVL470 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones
15 Series - Electronic step relay and dimmer. Features 15.91 15.51 15.81 SERIE
Series - Electronic step relay and dimmer SERIE Features.91.51.81 Electronic step relay and dimmer for control of lighting levels Suitable for incandescent and halogen lighting loads (with or without transformer
PCS0100en 02.2008. Persy Control Services B.V. Netherlands
P-Bus Gateway PBGW2.128 Universal gateway between the P-bus protocol and open standard protocols. The variety of available electrical interfaces on the gateway offers a wide range of possibilities for
ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL
RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,
CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems
CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems EN Security System CM705B CM705B - Universal Expander Module The CM705B universal expander provides a cost effective way